UPS5000-S-880 kVA
User Manual (CMI)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
110
Item
Description
Default Value Value Range
20 ms) occurs when the UPS
transfers from mains inverter
mode to bypass mode. If
Output
Freq. Track Rate
is fast, the
inverter frequency is unstable.
Bypass Settings
Figure 4-25
Bypass settings
Item
Description
Default Value Value Range
Maximum
bypass voltage
When the difference between the
bypass voltage and the rated
voltage is greater than this value,
the system determines that the
bypass voltage is abnormal and
that the bypass is unavailable.
When the voltage level is 380 V,
the value can be +10%, +15%,
+20%, or +25%. The default
value is +15%.
When the voltage level is 400 V,
the value can be +10%, +15%, or
+20%. The default value is
+15%.
When the voltage level is 415 V,
the value can be +10% or +15%.
The default value is +10%.
Minimum
bypass voltage
When the difference between the
bypass voltage and the rated
voltage is greater than this value,
the system determines that the
bypass voltage is abnormal and
that the bypass is unavailable.
–20%
–10%, –15%, –
20%, –30%, –
40%, –50%, –
60%
Bypass
frequency
range (Hz)
When the difference between the
bypass input frequency and the
rated frequency is greater than
the specified value, the system
determines that the bypass
±2 Hz
±0.5 Hz to ±6
Hz