Battery Mode
In battery mode, press and hold OFF/ENTER for more than 5s. Release the button
when you hear the buzzer buzzing. The UPS in battery mode is shut down.
Shutting Down the Inverter to Transfer the UPS to the No Output State
Step 1 Shut down loads.
Step 2 Perform the startup operation on the UPS. The UPS shuts down the inverter and
transfers to bypass mode. If mains parameters are inconsistent with bypass
parameters, the UPS transfers to standby mode.
Step 3 Switch off the AC input circuit breaker K
m
and output circuit breaker Q for the
UPS. After all indicators turn off and fans stop, the UPS shuts down and the loads
power off.
----End
5.2.3 Performing EPO
Turn on the EPO switch (provided by the customer). The UPS enters the EPO state.
That is, the UPS shuts down the inverter, and does not transfer to the bypass
mode.
Figure 5-7 EPO cable connection on a single UPS
5.3 Parallel System Operations
UPS2000-G-6KRTLL
User Manual
5 Operations
Issue 01 (2020-08-06)
Copyright © Huawei Technologies Co., Ltd.
80