UPS2000-A-(6 kVA-10 kVA)
User Manual
9 Technical Specifications
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
123
Item
6 kVA/10
kVA
Standard
Version with
Standard
Backup Time
6 kVA/10
kVA
Standard
Version
with Long
Backup
Time
6 kVA/10
kVA
Professional
Version
with
Standard
Backup
Time
6 kVA/10
kVA
Professional
Version
with Long
Backup
Time
minute. The input circuit breaker may trip in advance.
Load ≥ 150%: The UPS stops power output after 200 ms. The
input circuit breaker may trip in advance (load is calculated
based on the bypass currents).
Input mode
Single mains
9.5 Output Electrical Specifications
Item
6 kVA/10
kVA
Standard
Version with
Standard
Backup Time
6 kVA/10
kVA
Standard
Version
with Long
Backup
Time
6 kVA/10
kVA
Professional
Version
with
Standard
Backup
Time
6 kVA/10
kVA
Professional
Version
with Long
Backup
Time
Rated capacity
6 kVA/10 kVA
Output power factor
0.9 (When the power factor ranges from 0.5 to 1, the UPS2000-A
with inductive load is not derated. When the power factor ranges
from 0.5 to 1, the UPS2000-A with 80%–100% capacitive load is
linearly derated.)
Rated output voltage
220V AC/230V AC/240V AC
(selected by setting a voltage
level on the LCD.)
208 V AC/220 V AC/230 V
AC /240 V AC (selected by
setting a voltage level on the
LCD. The power is derated to
0.9 in 208 V mode.)
Output voltage
precision
±1%
Total harmonic
distortion of the
output voltage
waveform (THDv)
≤ 5% (configured with a residual current device (RCD) with a
0.7 power factor, and specified in the IEC62040 standards of
THDv.)
≤ 2% (resistive load. Each harmonic meets the limit specified
by the IEC62040.)
Crest factor
A maximum of 3:1