UPS2000-A-(6 kVA-10 kVA)
User Manual
4 Control Panel
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
76
Na
me
LCD
Function
Value
Range
Preset
Value
Remarks
Up
per
volt
age
thre
sho
ld
Upper
threshold
for the
ECO
voltage. In
ECO mode,
when the
difference
between
the bypass
voltage and
the rated
output
voltage
exceeds
this value,
the system
determines
that the
ECO
voltage is
abnormal
and
transfers to
normal
mode.
5%, 6%,
7%, 8%,
9%, and
10%
10%
The value
is
configura
ble only
after the
inverter
shuts
down.
Lo
wer
volt
age
thre
sho
ld
Lower
threshold
for the
ECO
voltage. In
ECO mode,
when the
difference
between
the bypass
voltage and
the rated
output
voltage
exceeds
this value,
the system
determines
that the
ECO
voltage is
abnormal
and
transfers to
normal
5%, 6%,
7%, 8%,
9%, and
10%
10%
The value
is
configura
ble only
after the
inverter
shuts
down.