UPS2000-A-(6 kVA-10 kVA)
User Manual
9 Technical Specifications
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
125
Item
UPS2000-A-6
kVA/10 kVA
Standard
Version
with
Standard
Backup
Time
UPS2000-A-6
kVA/10 kVA
Standard
Version
with Long
Backup
Time
UPS2000-A-6
kVA/10 kVA
Professional
Version
with
Standard
Backup
Time
UPS2000-A-6
kVA/10 kVA
Professional
Version
with Long
Backup
Time
Battery type of the
UPS2000-A with
standard backup time
12 V DC valve regulated lead acid (VRLA) battery
Battery capacity of
the UPS2000-A with
standard backup time
6 kVA: 7
Ah
10 kVA: 9
Ah
N/A
6 kVA: 7
Ah
10 kVA: 9
Ah
N/A
Power backup time
6 kVA: 4.8
minutes (at
full load
with a 0.9
power
factor), 5.6
minutes (at
80% load
with a 0.9
power
factor)
10 kVA:
3.7
minutes (at
full load
with a 0.9
power
factor), 4.8
minutes (at
80% load
with a 0.9
power
factor)
Determined
by the battery
capacity.
For the
power
backup
time of the
battery box
for the 6
kVA UPS,
see
For the
power
backup
time of the
battery box
for the 10
kVA UPS,
see
6 kVA: > 4
minutes (at
full load
with a 0.9
power
factor), 10
minutes (at
80% load
with a 0.9
power
factor)
10 kVA: >
4 minutes
(at full
load with a
0.9 power
factor), 5.9
minutes (at
80% load
with a 0.9
power
factor)
Determined
by the battery
capacity.
For the
power
backup
time of the
battery box
for the 6
kVA UPS,
see
For the
power
backup
time of the
battery box
for the 10
kVA UPS,
see
Parallel feature
A maximum of four battery strings are connected in parallel. That
is, a maximum of two battery boxes are installed.
Rated charger charge
current
2 A
4 A by
default; 1–8 A
configurable,
tolerance ±0.5
A
2 A
4 A by
default; 1–8 A
configurable,
tolerance ±0.5
A
Charger charge time
Batteries are
charged to
more than
90% in 3
Determined
by the battery
capacity.
Batteries are
charged to
more than
90% in 3
Determined
by the battery
capacity.