TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
4 Maintenance
Issue 02 (2019-02-26)
Copyright © Huawei Technologies Co., Ltd.
50
4.2.17 Water Alarm
This alarm is generated only for the power system that has a water sensor installed.
Possible Causes
There is water inside the cabinet.
The water sensor is faulty.
Measures
1.
Check whether there is water inside the cabinet. If so, remove the water with dry cotton
or other tools and then locate and rectify the fault.
2.
Check whether the water sensor is faulty. If the water sensor is faulty, replace it.
4.2.18 Smoke Alarm
This alarm is generated only for the power system that has a smoke sensor installed.
Possible Causes
There is smoke inside the cabinet.
The smoke sensor is faulty.
Measures
1.
Check whether there is smoke inside the cabinet. If so, disconnect the power supply from
the cabinet, handle the fault, and then restart the system and clear the alarm on the SMU.
2.
Check whether the smoke sensor is faulty. If the smoke sensor is faulty, replace it.
4.2.19 Rect Fault
Possible Causes
Rectifier connections are loose.
A rectifier is faulty.
Measures
1.
Check the Fault indicator on the rectifier panel. If it is steady red, remove the rectifier,
and then reinstall it after the indicator turns off.
2.
If the alarm persists, replace the rectifier.
4.2.20 Rect Protection
Possible Causes
The rectifier input voltage is too high.
The rectifier input voltage is too low.
The ambient temperature is too high.