TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
2 Components
Issue 02 (2019-02-26)
Copyright © Huawei Technologies Co., Ltd.
11
breaker
(neutral wire)
device (SPD)
Figure 2-4
AC output unit (Multi-purpose socket and RCD)
(1) All-purpose socket
(2) RCD
(3) AC load circuit breaker and neutral wire terminal
describes the AC PDU configurations for the TP48200A-HX09A2.
Table 2-1
AC PDU configurations
Power Grid
Mode
AC Input
Circuit
Breaker
AC Surge
Protection
Class
AC Load
Circuit
Breaker
Maintenance Socket
and Its Protection Mode
110 V AC
dual-live-wire
One
2-pole 125
A circuit
breaker
Class B. The
normal current
(In) is 30 kA,
and the
maximum
current (Imax) is
60 kA.
One
2-pole 10
A circuit
breaker
Multi-purpose socket and
10 A residual current
device (RCD).
NOTE
110 V AC dual–live wire
input:
There is a neutral wire by
default and the
maintenance output
voltage is 110 V AC. If
you need an output
voltage of 220 V AC,
change the cable
connections to the
maintenance socket based
on
If there is no neutral wire,
change the cable