7.2 Troubleshooting
Alarm severities are defined as follows:
Major: The inverter is faulty. As a result, the output power decreases or the grid-tied
power generation is stopped.
Minor: Some components are faulty without affecting the grid-tied power generation.
Warning: The inverter works properly. The output power decreases or some authorization
functions fail due to external factors.
Table 7-2
Common alarms and troubleshooting measures
Alarm ID Alarm
Name
Alarm
Severity
Possible Cause
Troubleshooting Suggestion
2001
High
String
Input
Voltage
Major
Excessive PV modules are
connected in series in the PV
array. Therefore, the open-
circuit voltage exceeds the
maximum input voltage of the
SUN2000.
Cause ID 1 = PV1
Cause ID 2 = PV2
Check the number of PV modules
connected in series in the PV string,
and ensure that the PV string open-
circuit voltage is no greater than the
maximum operating voltage of the
SUN2000. After you correctly
configure the PV array, the inverter
alarm disappears automatically.
2002
DC Arc
Fault
Major
The PV string power cable
arcs or is in poor contact.
Cause ID 1 = PV1
Cause ID 2 = PV2
Check whether the string cables arc
or are in poor contact.
2011
String
Reversed
Major
The PV string is reversely
connected.
Cause ID 1 = PV1
Cause ID 2 = PV2
Check whether the PV string is
reversely connected to the
SUN2000. If so, wait until the solar
irradiance declines at night and the
PV string current drops to below 0.5
A. Then, set the
DC SWITCH
to
the
OFF
position, and correct the
string polarity.
2012
String
Current
Backfeed
Warning
Only a few PV modules are
connected in series in the PV
string. Therefore, the end
voltage is lower than that of
other PV strings.
Cause ID 1 = PV1
Cause ID 2 = PV2
1.
Check whether the PV modules
connected in series in the PV
string are enough. If not, add
more modules.
2.
Check whether the PV string is
shaded.
3.
Check whether the open-circuit
voltage of the PV string is
normal.
2031
Power
grid phase
wire
short-
circuit to
PE
Major
Cause ID = 1
The impedance of the output
phase wire is low or short-
circuited to PE.
Check the impedance of the output
phase wire to PE, locate the position
with lower impedance and restore
that.