No.
Parameter
Description
Unit
Value Range
1
Unbalance
voltage protection
Specifies the SUN2000 protection
threshold in the case of unbalanced
power grid voltage.
%
[0.0, 50.0]
2
Phase angle offset
protection
The standards of certain countries and
regions require that the SUN2000 needs
to be protected when the three-phase
angle offset of the power grid exceeds a
certain value.
N/A
Disable
Enable
3
10 minute OV
protection
Specifies the 10-minute overvoltage
protection threshold.
V
[1 x Vn, 1.36 x Vn]
4
10 minute OV
protection time
Specifies the 10-minute overvoltage
protection duration.
ms
[50, 7200000]
5
Level-1 OV
protection
Specifies the level-1 overvoltage
protection threshold.
V
[1 x Vn, 1.36 x Vn]
6
Level-1 OV
protection time
Specifies the level-1 overvoltage
protection duration.
ms
[50, 7200000]
7
Level-2 OV
protection
Specifies the level-2 overvoltage
protection threshold.
V
[1 x Vn, 1.36 x Vn]
8
Level-2 OV
protection time
Specifies the level-2 overvoltage
protection duration.
ms
[50, 7200000]
9
Level-1 UV
protection
Specifies the level-1 undervoltage
protection threshold.
V
[0.15 x Vn, 1 x Vn]
10
Level-1 UV
protection time
Specifies the level-1 undervoltage
protection duration.
ms
[50, 7200000]
11
Level-2 UV
protection
Specifies the level-2 undervoltage
protection threshold.
V
[0.15 x Vn, 1 x Vn]
12
Level-2 UV
protection time
Specifies the level-2 undervoltage
protection duration.
ms
[50, 7200000]
13
Level-1 OF
protection
Specifies the level-1 overfrequency
protection threshold.
Hz
[1 x Fn, 1.15 x Fn]
14
Level-1 OF
protection time
Specifies the level-1 overfrequency
protection duration.
ms
[50, 7200000]
15
Level-2 OF
protection
Specifies the level-2 overfrequency
protection threshold.
Hz
[1 x Fn, 1.15 x Fn]
16
Level-2 OF
protection time
Specifies the level-2 overfrequency
protection duration.
ms
[50, 7200000]
17
Level-1 UF
protection
Specifies the level-1 underfrequency
protection threshold.
Hz
[0.85 x Fn, 1 x Fn]
18
Level-1 UF
protection time
Specifies the level-1 underfrequency
protection duration.
ms
[50, 7200000]