SUN2000-(55KTL, 60KTL) Series
User Manual
6 System Commissioning
Issue 06 (2020-01-03)
Copyright © Huawei Technologies Co., Ltd.
64
Figure 6-7
Quick Settings (advanced user)
Set the power grid code that applies to the country or region where the PV plant is located and the
SUN2000 model.
Set user parameters based on the current date and time.
Set
Baud rate
,
RS485 protocol
, and
Address
based on site requirements.
Baud rate
can be set to
4800
,
9600
, or
19200
.
RS485 protocol
can be set to
MODBUS RTU
, and
Address
can be set to any
value in the range of 1 to 247.
When multiple SUN2000s communicate with the SmartLogger over RS485, the RS485 addresses
for all the SUN2000s on each RS485 route must be within the address range set on the SmartLogger
and cannot be duplicate. Otherwise, the communication will fail. In addition, the baud rates of all the
SUN2000s on each RS485 route must be consistent with the SmartLogger baud rate.