No.
Parameter
Description
Unit
Value Range
Remarks
3
Maximum
apparent
power
Specifies the output upper
threshold for the
maximum apparent power
to adapt to the capacity
requirements for standard
and customized
transformers.
kVA
[Maximum active
power, Smax_limit]
If the maximum
active power equals
Smax_limit, this
parameter is not
displayed.
4
Maximum
active power
Specifies the output upper
threshold for the
maximum active power to
adapt to various market
requirements.
kW
[0.1, Pmax_limit]
Pmax_limit
is the
upper limit of the
maximum active
power.
5
Shutdown at
0% power
limit
If this parameter is set to
Enable
, the SUN2000
shuts down after receiving
the 0% power limit
command. If this
parameter is set to
Disable
, the SUN2000
does not shut down after
receiving the 0% power
limit command.
N/A
Disable
Enable
N/A
6
Active power
change
gradient
Adjusts the change speed
of the SUN2000 active
power.
%/s
[0.1, 1000]
Adjust the active
power based on the
percentage of the
rated apparent power.
7
Fixed active
power
derated
Adjusts the active power
output of the SUN2000 to
a fixed value.
kW
[0, Pmax_limit]
Pmax_limit
is the
upper limit of the
maximum active
power.
8
Active power
percentage
derating
Adjusts the active power
output of the SUN2000 to
a percentage.
%
[0, 100]
If this parameter is
set to
100
, the
SUN2000 delivers
power output based
on the maximum
output power.
9
Reactive
power output
at night
In some specific
application scenarios, a
power grid company
requires that the
SUN2000 can perform
reactive power
compensation at night to
ensure that the power
factor of the local power
grid meets requirements.
N/A
Disable
Enable
This parameter is
configurable only
when
Isolation
is set
to
Input
ungrounded, with a
transformer
.