SUN2000-(33KTL, 40KTL)
User Manual
7 User Interface
Issue 03 (2015-12-01)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
71
Indicator
Status
Meaning
Blinking green slowly (on for 1s and
then off for 1s)
There is an operation with
a USB flash drive.
Blinking green fast (on for 0.125s
and off for 0.125s)
An operation with a USB
flash drive has failed.
Steady green
An operation with a USB
flash drive is successful.
----End
7.1.3 Exporting Data
Export the inverter data through a USB flash drive.
Context
USB flash drives of SanDisk, Kingston, and Netac are recommended. Other brands may be
incompatible.
Procedure
Step 1
On the SUN2000 local commissioning tool, click
Inverter Command Settings
to generate a
boot script file. For details, see
SUN2000 APP User Manual
.
Step 2
Import the boot script file to the root directory of a USB flash drive.
Step 3
Connect the USB flash drive to the USB port. The system automatically identifies the USB
flash drive and executes all commands specified in the boot script file. View the LED
indicator to determine the operating status.
Verify that the ciphertext in the boot script file matches the login password of the SUN2000
APP. Otherwise, after you insert the USB flash drive for five consecutive times, the user
account will be locked for 10 minutes.
Table 7-3
Indicator status
Indicator
Status
Meaning
Off
There is no operation with
a USB flash drive.
Blinking green slowly (on for 1s and
then off for 1s)
There is an operation with
a USB flash drive.
Blinking green fast (on for 0.125s
An operation with a USB