6 Electrical Connections (12-pin Spot-Check Terminal)
Issue 07 (2019-06-30)
Copyright © Huawei Technologies Co., Ltd.
67
Figure 6-2
Keeping the door open with a support bar
----End
6.2 Connecting a Ground Cable to the PE Point
Prerequisites
The ground cable and OT terminal are available.
Ground cable: outdoor copper cable with a cross-sectional area greater than or equal to
5.5 mm
2
The SUN2000 is grounded in type A or C mode.
OT terminal: M6
Context
The ground point on the enclosure is preferred to connect to the PE cable for the
SUN2000.
The ground point in the maintenance compartment is mainly used for connecting to the
ground cable included in the multi-core AC power cable. For details, see
6.3 Installing the AC Output Power Cable
There are two ground points on the enclosure shell and one of them is standby.
It is recommended that the ground cable be connected to a nearby ground point. For a
system with multiple SUN2000s connected in parallel, connect the ground points of all
SUN2000s to ensure equipotential connections to ground cables.
Procedure
Step 1
Strip an appropriate length of the insulation layer using a wire stripper, as shown in