10 Monitoring Batteries by Using iBAT 2.0 

 

Issue 08 (2020-01-09) 

Copyright © Huawei Technologies Co., Ltd. 

73 

 

8.

 

Ensure that the number of BIMs for a battery string is the same as the number of 
batteries in the battery string set on the 

Config

 > 

Comm. Config

 page, and is not greater 

than the number of batteries in the battery string set on this page. 

Step 7

 

Verify whether the operation is correct. Choose 

Monitoring

 > 

Real-Time Data

 > 

Battery 

String Settings

, and you can view the data of batteries. Choose 

Monitoring

 > 

Active alarms

and there is no alarm (such as CIM number inconsistency, BIM communication failure). Then 
the operation is correct. If the operation is incorrect, check whether each step is performed 
correctly. 

----End 

10.3 CIM Control 

On the WebUI, choose 

Monitoring

 > 

Control

 > 

CIM Control

 to control and maintain the 

CIMs and BIMs. For details, see 

4.4.4 Control Page

. 

Summary of Contents for RMS-SNMP01A

Page 1: ...RMS SNMP01A SNMP Card User Manual Issue 08 Date 2020 01 09 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ...tomer All or part of the products services and features described in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to c...

Page 3: ...rt for RMS SNMP01A Intended Audience This document is intended for Sales engineer Technical support engineer System engineer Hardware installation engineer Commissioning engineer Data configuration engineer Maintenance engineer Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates a hazard with a high level of risk which if not avoide...

Page 4: ... History Changes between document issues are cumulative The latest document issue contains all the changes made in earlier issues Issue 08 2020 01 09 Deleted the Modbus TCP feature Issue 07 2019 12 20 Updated the safety information Issue 06 2019 11 26 Updated the SNMP version description Issue 05 2019 10 18 Updated the GSM description Issue 04 2017 01 19 Added the DHCP feature Added the external d...

Page 5: ...r Manual About This Document Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd iv Updated the software The document name changed to RMS SNMP01A V100R002 SNMP Card User Manual Issue 01 2015 08 18 This is the first release ...

Page 6: ...ts 10 3 5 1 Temperature and Humidity Sensor 10 3 5 2 AI DI Module 11 3 5 3 GSM Modem 14 3 5 4 iBAT 2 0 15 3 5 5 External Dry Contact Card 18 4 Managing the UPS on the WebUI 20 4 1 Introduction to Web Pages 20 4 2 Preparations for Login 21 4 2 1 Installing an HTTPS Certificate for the Web Browser 21 4 2 2 Setting Internet Explorer Options 24 4 2 3 Privacy Statement 26 4 3 WebUI Login 27 4 4 Monitor...

Page 7: ...ibrary 63 6 3 Managing the UPS by Using the NMS 63 6 3 1 Applying for Access Rights 63 6 3 2 Managing the UPS 63 7 Managing the UPS by Using the NMS Complying with RFC1628 Standard 64 7 1 Installing the UPS MIB Library 64 7 2 Managing the UPS by Using the NMS 64 7 2 1 Applying for Access Rights 64 7 2 2 Managing the UPS 64 8 Protecting the Server by Using NetShutdown 65 8 1 Introduction to NetShut...

Page 8: ...nts Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd vii 12 Upgrading the SNMP Card 75 13 Changing the SSH Access Password 79 13 1 Maintenance Suggestions 79 13 2 Changing an Authentication Password 80 A Acronyms and Abbreviations 83 ...

Page 9: ...he SNMP card on the WebUI For details see section 4 6 2 User Mgmt Page 4 Change the preset password in your first login to the SNMP card over Secure Shell SSH For details see section 13 2 Changing an Authentication Password 5 Exercise caution when manually shutting down the UPS inverter for transferring to bypass mode or when adjusting the UPS output voltage level or frequency Doing so may affect ...

Page 10: ...UAWEI_UPS_MIB library or UPS RFC1628 MIB library can be downloaded from its own web page instead of any CD ROM Enables remote management on Windows or Linux using a web browser The supported web browsers include Internet Explorer 8 Internet Explorer 9 Internet Explorer 10 Internet Explorer 11 and Firefox 33 1 Provides an access security mechanism assigns rights to users based on roles and implemen...

Page 11: ... SSH see section 13 2 Changing an Authentication Password 2 2 Port Description Figure 2 1 shows the ports on the SNMP card Figure 2 1 Ports 1 Port for southbound device 2 USB port GSM modem supported 3 RS485 southbound interface 4 Ethernet port The NETWORK port of SNMP card is an RJ45 port It communicates with the 10 Mbps 100 Mbps Ethernet over a standard network cable The indicators show the comm...

Page 12: ...ort and TEM_HUM port use Modbus protocol without reference to the access authentication mechanism The USB port connects to the GSM modem without reference to the system management The SNMP card is equipped with a temperature and humidity sensor or an external dry contact card over an RS485 bus Table 2 2 lists the port definition Table 2 2 TEM_HUM port Port Pin No Signal Port Type J3004 1 GND RJ11 ...

Page 13: ...RMS SNMP01A SNMP Card User Manual 2 Overview Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 5 Port Pin No Signal Port Type 4 RS485 5 RS485 6 N A 7 N A 8 N A ...

Page 14: ...llips screwdriver Electrostatic discharge ESD gloves 3 2 Precautions The SNMP card supports hot swap when it is not equipped with a temperature and humidity sensor The SNMP card does not support hot swap when it is equipped with a temperature and humidity sensor Some electronic components in the SNMP card are sensitive to ESD Do not use your hands or electrical objects to touch electronic componen...

Page 15: ...on different UPSs of Huawei The SNMP card is installed in the optional card slot INTELLISLOT at the rear panel of the UPS Procedure Step 1 Remove the cover of the optional card slot on the real panel of the UPS as shown in Figure 3 1 Figure 3 1 Removing the cover of the optional card slot Store the cover well for future use Step 2 Insert the SNMP card into the slot and tighten screws as shown in F...

Page 16: ...NMP card and the other end to an Ethernet port If the green indicator turns on and the yellow indicator blinks the SNMP card is successfully installed and is properly communicating with the Ethernet End 3 4 Setting an IP Address for the SNMP Card The factory settings are as follows IP address 192 168 0 10 Sub mask 255 255 255 0 Gateway 192 168 0 1 The preceding are the default values of IP address...

Page 17: ...Co Ltd 9 Procedure Step 1 Press on the LCD On the Main Menu choose Settings Step 2 Enter a password The preset password is 000001 Step 3 Select Communication Card Step 4 Press The Communication Card screen is displayed Step 5 On the Communication Card screen set an IP address Sub mask and Gateway for the SNMP card End ...

Page 18: ... to the temperature and humidity sensor document set the temperature and humidity sensor address to 1 toggle switch 1 is ON and other toggle switches are OFF for ENR1DETA MODULE as shown in Figure 3 3 and baud rate to 9600 Figure 3 3 DIP switch on the ambient temperature and humidity sensor RJ11 Terminal The temperature and humidity sensor connects to an SNMP card over a symmetric twisted pair If ...

Page 19: ...the SNMP Card RJ11 Terminal Signal ENR1DETA MODULE RJ11 Terminal Signal X1 1 GND GND X1 2 N A N A X1 3 RS485 RS485 X1 4 RS485 RS485 X1 5 N A N A X1 6 12 V 12 V 3 5 2 AI DI Module AI DI_1 is a 12 V level output port that cannot connect to an external power source AI DI Module Types The SNMP card supports only one AI DI module and its model is MUE06A If the SNMP card is configured with the AI DI mod...

Page 20: ...When the signal is unstable due to signal reflection which is caused by the long communication route greater than 200 m set toggle switch 4 to ON for the farthest AI DI module as shown in Figure 3 5 After the DIP switch settings are modified power off and restart the AI DI module for the new settings to take effect The AI DI_1 port can connect to the UPS run indicator Table 3 3 shows the indicator...

Page 21: ...card and the other end into the COM_IN port on the AI DI module Figure 3 6 shows the RJ45 terminals Figure 3 6 RJ45 terminals As shown by View A in Figure 3 6 the pins are X1 1 to X1 8 from left to right Table 3 4 describes the mapping between wiring terminals Table 3 4 Mapping between wiring terminals Connecting to SNMP Card Connecting to AI DI Module RJ45 Terminal Connecting to SNMP Card RJ45 Te...

Page 22: ...If a GSM modem is configured for the SNMP card and a SIM card is inserted properly users can view the SMS module status indicating that the SMS module is present in the communication status bar of the WebUI as shown in Figure 4 9 If a GSM modem is not configured the status indicates that the SMS module is not present Only the SMS function of the GSM modem is used This function enables information ...

Page 23: ...imates the battery health status and uploads data to the SNMP card through the COM port An external Hall effect sensor is connected to the CIM to monitor the current of each battery string The BIM is a battery monitoring module that monitors the voltages internal resistances and pole temperatures of batteries It uploads battery data to the CIM through wireless communication Connecting the CIM and ...

Page 24: ...SNMP card If both the CIMs and independent AI DI module are deployed cascade the CIMs with the independent AI DI module as shown in Figure 3 11 When the SNMP card connects to the CIMs the DIP switches of the CIMs need to be set The DIP switch of the first CIM must be set to the start address 0000 and the DIP switches of the CIMs must be consecutive If the number of CIMs is 4 then the DIP switch of...

Page 25: ...f the Hall effect sensor is 50 A set Current source to Hall 50 A If the Hall current sensor is prepared by the customer the customer should refer to the model recommended by Huawei The rated current of the sensor should be 50 A 100 A and so on and the corresponding output voltage at rated current should be 4 V For example if the 0 50 A Hall sensor range is chosen ensure that the sampling current 5...

Page 26: ...eight battery routes 2 12 V 12 V 3 AI M 4 GND GND Arrange the positive and negative Hall effect sensor cables based on the battery string number in the sequence of first positive and then negative 3 5 5 External Dry Contact Card An external dry contact card can be configured for the SNMP card You are advised to configure an external dry contact card of the model RMS RELAY02B Figure 3 13 External d...

Page 27: ...t cables to the external dry contact card The RMS SNMP01A card does not support connection to a temperature and humidity sensor and an external dry contact card at the same time Figure 3 14 Connecting cables to the external dry contact card Refer to the external dry contact card user manual and set the card address to 8 Figure 3 15 shows the DIP switch status of the RMS RELAY02B 1 is set to ON and...

Page 28: ...reset the CIM and BIM perform blinking and measure internal resistances Query page The Logs page allows you to query users operation information to know recent operations The Performance Data page displays the performance data of each UPS You can query and export the performance data of a selected UPS The Historical Alarms page displays alarms of each UPS You can query and export the historical al...

Page 29: ... the performance data and historical alarms of a single UPS or all UPSs The Upgrade page allows you to upgrade the SNMP card software For the UPS2000 A you can also upgrade the UPS software 4 2 Preparations for Login 4 2 1 Installing an HTTPS Certificate for the Web Browser Open the web browser Internet Explorer 8 as an example In the address box enter the SNMP card IP address to open the login pa...

Page 30: ...chnologies Co Ltd 22 Figure 4 2 Certificate Invalid dialog box Click View Certificates in Figure 4 2 The dialog box providing the Certificate is displayed as shown in Figure 4 3 Figure 4 3 Certificate dialog box You can identify the cause of the following certificate error messages according to Figure 4 3 ...

Page 31: ...the root certificate for the digital certificate of the web server in the Trusted Root Certification Authorities folder on the Windows computer The installation procedure is as follows Click Install Certificate as shown in Figure 4 3 Choose Place all certificates in the following store and install the certificate in the Trusted Root Certification Authorities folder as shown in Figure 4 4 Figure 4 ...

Page 32: ...ethod 1 In Internet Explorer choose Internet Options Advanced Deselect Warn about certificate address mismatch as shown in Figure 4 5 Method 2 Apply for a digital certificate again Figure 4 5 Setting Internet options 4 2 2 Setting Internet Explorer Options Choose Internet Options Advanced and set options as shown in Figure 4 6 ...

Page 33: ... 2 is selected in Internet Explorer 8 or Internet Explorer 9 web pages cannot be accessed If Internet Explorer 10 or Internet Explorer 11 needs to be used to access web pages you must add the compatibility view settings Choose Page Compatibility View Settings and add the SNMP card IP address If the SNMP card IP address is not changed add 192 168 0 10 as shown in Figure 4 7 ...

Page 34: ...om the customer anonymize the user information in accordance with national or local legal requirements and delete recorded files after the fault locating is complete The UPS2000 system logs email sending and GSM modem function may involve system or personal information Log To facilitate fault location the UPS2000 system may record the following information in logs detailed data exchange and proces...

Page 35: ... a short message to users Users can send short messages to query the system status and active alarms This function may involve system and personal information including the device information and mobile number The system displays part of a mobile number For example the system displays 01415478578 as 014 8578 on the WebUI The system provides the personal data encryption protection Mobile numbers ar...

Page 36: ...control System configuration communication configuration user management site configuration performance data SNMP and RCCMD System maintenance upgrade operation record maintenance performance data maintenance historical alarms maintenance serviceable data maintenance and CIM E Label guest N A Only browses system running information without permission to perform any system changes There is no verif...

Page 37: ...UPS model and ESN The UPS information area presents Active Alarms as shown in Figure 4 9 Click the device name on the upper left corner to edit it or edit it by pressing Enter Figure 4 9 Monitoring page Table 4 2 Description of the Monitoring page Area Function Navigation area Lists the monitored UPSs Main menu bar Displays the main menus Monitoring Query Config and Maintenance Alarm quantity disp...

Page 38: ...ime Data Page In the UPS information area click Real Time Data UPS you can view the UPS running data on the Real Time Data page The data includes the input voltage and frequency bypass voltage and frequency output voltage current frequency load ratio power battery voltage current temperature and backup time Figure 4 10 is shown in the UPS running diagram If the CIM function is used in the UPS info...

Page 39: ...RMS SNMP01A SNMP Card User Manual 4 Managing the UPS on the WebUI Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 31 Figure 4 10 Real time data UPS Figure 4 11 Real time data battery string ...

Page 40: ...4 3 Default parameter values and value ranges Parameter Default Value Value Range Overtemperature threshold 40 C 30 60 C Undertemperature threshold 0 C 30º C to 10 C Overhumidity threshold 90 RH 70 100 RH Underhumidity threshold 10 RH 0 40 RH If a CIM is configured in the UPS information area choose Param Settings Battery String Settings and you can set the battery strings connected to each UPS as...

Page 41: ...nfig Page After the value of Number of battery strings or Number of batteries in a battery string is modified and submitted successfully the battery string information will be cleared Number of battery strings and Number of batteries in a battery string refer to information about the battery strings connected to the UPS The parameters are not sent to the CIMs The SNMP card associates the battery s...

Page 42: ...y after long time 60 days by default battery charging Capacity test A manual deep discharge test designed to obtain the battery discharge performance data You can perform the following operations on the Control page When the shallow discharge test conditions are met click Start to perform a shallow discharge test When the capacity test conditions are met click Start to perform a capacity test Afte...

Page 43: ...he board to reset 2 Blink After you select a BIM the RUN ALM indicator of the corresponding BIM will blink green at super short intervals to locate the actual BIM If an indicator blinks at long intervals it is blinking on for 1s and then off for 1s If an indicator blinks at super short intervals it is blinking at 10 Hz that is on for 0 05s and then off for 0 05s 3 Measure internal resistance When ...

Page 44: ...4 16 It lists a maximum of 1000 records Figure 4 16 Logs page 4 5 2 Performance Data The Performance Data page records UPS working performance data including the input voltage and frequency and output voltage current frequency and load ratio information Select Performance Data in the Query at the first menu level to enter the performance statistics page as shown in Figure 4 17 Figure 4 17 Performa...

Page 45: ...orical Alarms from the menu at the first level Then you can query historical alarms in a specified time period as shown in Figure 4 19 Figure 4 19 Historical Alarms page Select an alarm severity critical major minor or warning select the device set the start time and end time and click Query The page displays historical alarms in the specified time period for the selected UPS as shown in Figure 4 ...

Page 46: ...ault as shown in Figure 4 21 You can also click User Mgmt Site Config Performance Data SNMP and RCCMD The Comm Config page allows you to change the system IP settings and configure a sender s email and configure an alarm notification perform RMS RELAY02B settings CIM settings and CIM information settings Changing the IP Address of the SNMP Card Under System IP Settings change the SNMP card IP addr...

Page 47: ...ange You are advised to select When the IP address is automatically assigned send an email If DHCP fails to be allocated the IP address of the SNMP card will restore to the default IP address 192 168 0 10 and the DHCP will be deselected If DHCP is selected and the IP address expires during SNMP card power off the IP address will be reallocated after the SNMP card starts If DHCP is selected and DHC...

Page 48: ...hoose whether to enable email and SMS notifications requiring a GSM modem Timely Reminder and select alarm severities critical major minor or All as shown in Figure 4 21 The user name and SMS notification receiver number can be configured on the User Mgmt tab If you enable alarm notification by email or SMS when there is an alarm the system will send emails or short messages to the receiver at 8 0...

Page 49: ...tatus by setting the DO type and associated event The SNMP card controls UPS startup shutdown based on the configured DI type and DI input status For DO1 to DO4 The NO and COM pins of DO are closed and the NC and COM pins of DO are open when the associated event is consistent with the UPS status otherwise the NC and COM pins of DO are closed and the NO and COM pins of DO are open For DI1 and DI2 I...

Page 50: ...DO1 Bypass mode Mains mode NC and COM pins of DO are closed NO and COM pins of DO are open Table 4 6 Association between DI status and UPS status Name Type Associated Event DI Status Execute Event or Not DI1 NO Startup There is a 12 24 V DC input Yes DI1 NC Startup There is a 12 24 V DC input No DI1 NO Startup There is no input No DI1 NC Startup There is no input Yes CIM Settings If CIMs are used ...

Page 51: ...battery string under the CIM On the Monitoring Param Settings page when you set the battery strings the number of BIMs of a single battery string under the CIM cannot exceed the number of batteries in each battery string set here Number of battery strings connected to the CIM The number of battery strings under the CIM On the Monitoring Param Settings page when you set the battery strings the numb...

Page 52: ...gurations enter a mobile number used to receive alarm notification and SMS query results A GSM modem is required You can send a test message to check whether the GSM modem is available Click Submit to add the user The user name cannot exceed 20 characters and can contain only uppercase and lowercase letters digits and underscores The password contains 6 to 20 characters and at least two types of u...

Page 53: ...the local time To enable this specify a valid NTP server IP address and click Submit for the setting to take effect as shown in Figure 4 28 The SNMP card can also synchronize time from the NetEco1000U To enable this select a valid NetEco1000U IP address from the address list and click Submit for the setting to take effect as shown in Figure 4 29 You can set System name ups2000 as default System lo...

Page 54: ...S SNMP01A SNMP Card User Manual 4 Managing the UPS on the WebUI Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 46 Figure 4 27 Site Config page Figure 4 28 Time synchronization from the NTPserver ...

Page 55: ... Huawei Technologies Co Ltd 47 Figure 4 29 Time synchronization from the NetEco1000U Figure 4 30 Certificate management 4 6 4 Performance Data Page On the Performance Data page you can set Data recording period to 10s 30s default 1 min 5 min 10 min 15 min 30 min or 60 min as shown in Figure 4 31 ...

Page 56: ...ser as shown in Figure 4 33 and Figure 4 34 If you manage the UPS by using the NMS pay attention to this topic SNMP version has three options SNMPv1 SNMPv2c SNMPv3 and ALL Different versions support different NMS access mechanisms The default value is SNMPv3 The configured user name authentication protocol MD5 SHA and proprietary protocol DES AES are used by the NMS to access the SNMP card and add...

Page 57: ...ee options You are advised to use the secure protocol SNMPv3 When SNMPv3 is changed to ALL SNMPv1 SNMPv2c the system prompts SNMP V1 V2 is Insecure protocol When SNMPv1 SNMPv2c is used the correct read write community name must be configured for the NMS to connect to the SNMP card The standard encryption algorithms MD5 and DES have security risks You are advised to use the secure encryption algori...

Page 58: ...r SNMPv1 SNMPv2c not first time setting The default value of SNMP port is 161 which is subject to change If you use Huawei NetEco set SNMP port to 161 Click Download UPS RFC1628 MIB on the page to download the MIB file which allows a third party NMS complying with the RFC1628 standard such as UNMS of Generex to manage the UPS remotely Click Download HUAWEI UPS MIB to download the MIB file which al...

Page 59: ... a third party NMS complying with Huawei standard is adopted download the HUAWEI_UPS_MIB file For details about the function of a third party NMS managing UPS see 6 Managing the UPS by Using the NMS Complying with Huawei Standard Under NMS Address and Permission Settings you can add NMS information for accessing the SNMP card The information includes NMS Addr Permission as shown in Figure 4 36 SNM...

Page 60: ...nt cannot receive the correct shutdown command or event message For the ESN of the UPS see the manual delivered with the UPS ESN Configuration If a single UPS is online the ESN of the UPS is displayed by default The ESN cannot be set as shown in Figure 4 38 If the SNMP card is inserted into a parallel system the ESN is empty during first login Select the ESN of the UPS where the SNMP card is inser...

Page 61: ...ue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 53 Figure 4 39 RCCMD shutdown disabled Figure 4 40 RCCMD shutdown enabled SSL Encrypted Transmission The SSL encrypted transmission set on the UPS2000 SNMP card page must be the same as the setting on the RCCMD client ...

Page 62: ...n the page as shown in Figure 4 42 If the SSL Encrypted Transmission is set to Disabled a message indicating there is a risk will be displayed Figure 4 41 SSL encrypted transmission enabled by default Figure 4 42 SSL encrypted transmission disabled Event Configuration The SNMP card supports 17 alarm events and a maximum of 50 jobs can be added for each event as shown in Figure 4 43 Figure 4 43 sho...

Page 63: ...ng all You can view all jobs of all events by clicking this button 2 Button for expanding one event You can view all jobs of the event by clicking this button 3 Button for adding one job You can add one job for the event by clicking this button 4 Button for adding one job for events Select multiple events and you can add one job for the selected events at the same time by clicking this button 5 Bu...

Page 64: ...leting one job You can delete the job by clicking this button 3 Button for test If you click this button the job will be performed and a message showing test succeeds or fails will be displayed on the page Adding one job for one event Select one event for example Inverter on click the button for adding one job and the page for adding a job for the event is displayed When adding a job the job types...

Page 65: ...nstalled with the RCCMD software Figure 4 45 RCCMD shutdown RCCMD Message Specify the RCCMD client IP address port and message to be conveyed The RCCMD client will receive the message For example enter This is a test message Figure 4 46 RCCMD message RCCMD Execute Specify the RCCMD client IP address port and command to be executed For example enter SHUTDOWN and the RCCMD client will shut down the ...

Page 66: ...echanism If you want to define the TRAP message by yourself you can use the TRAP signal to display the UPS information For example if you enter INVOLT the RCCMD client will receive the UPS input voltage value for example single phase 220 three phase A 220 B 220 C 220 Table 4 9 lists the signal names that can be entered Figure 4 48 RCCMD TRAP Table 4 9 RCCMD TRAPsignal Signal Name Description Unit ...

Page 67: ... add a job five sending methods are available The latter three methods can take effect only when event condition is still true after the specified seconds Immediately once After the event happens the job will be sent to the RCCMD client immediately Scheduled in X seconds After the event happens the job will be sent to the RCCMD client once in X seconds No matter whether the event disappears or not...

Page 68: ...ate can be uploaded as shown in Figure 4 49 If the RCCMD certificate or RCCMD CA certificate is not uploaded the default certificate provided by the system is used for communication After the certificate is uploaded successfully click Submit The SNMP card WebUI will restart and the uploaded certificate will be used for communication Figure 4 49 RCCMD certificate management If the used RCCMD certif...

Page 69: ...tton a file download dialog box appears You can open or save the file Figure 4 50 Data Maintenance page 4 7 2 Upgrade Page The Upgrade page allows you to upgrade the SNMP card software For the UPS2000 A you can also upgrade the UPS software On the main menu bar click Maintenance The Upgrade page is displayed as shown in Figure 4 51 Figure 4 51 Upgrade page For details about the upgrade see chapter...

Page 70: ... and manage the UPS remotely which improves UPS centralized management and remote operation and maintenance The software is available at https support huawei com or https support huawei com enterprise 5 2 Applying for Access Rights To manage the UPS by using an SNMP card apply to the system administrator of the SNMP card for access rights and add the NMS information to the NMS access list of the S...

Page 71: ... mib files Download the MIB files on the web browser For details see section 4 6 1 Comm Config Page When you load the MIB library by using the NMS load the HUAWEI MIB V3 34 mib file and then the HUAWEI UPS MIB mib file For details see the NMS user manual 6 3 Managing the UPS by Using the NMS 6 3 1 Applying for Access Rights To manage the UPS by using an SNMP card apply to the system administrator ...

Page 72: ...need to set the ESN For a parallel system set the ESN of the UPS in which the SNMP card is located on the Config RCCMD page 7 2 Managing the UPS by Using the NMS 7 2 1 Applying for Access Rights To manage the UPS by using the UNMS of Generex over an SNMP card apply to the system administrator of the SNMP card for access rights and add the NMS information to the NMS access list of the SNMP card NMS...

Page 73: ...n implements the specified protection measures to protect your computer or server hardware and software assets 8 2 Adding NetShutdown Software to the SNMP Card To manage the UPS by using an SNMP card apply to the SNMP card system administrator for management rights and add IP address information of the PC corresponding to NetShutdown software to the SNMP card access list 8 3 Obtaining the UPS Stat...

Page 74: ... command or trap message to the RCCMD client Receives the message UPS alive check sent by the RCCMD client and replies with the system status Configures and saves the address and port for receiving the shutdown command and the message sending mechanism For the method of installing the RCCMD client see the manual related to the RCCMD 9 2 RCCMD Event Shutdown and Message Sending Procedure Step 1 On ...

Page 75: ...WebUI Step 4 Configure events If you set the job type to RCCMD Message under Inverter on specify the IP address and port of the RCCMD client The port is 6003 by default If you need to modify the port modify the port on the RCCMD client at the same time to keep them the same Enter the message to be sent and set the message sending mechanism For example set it to Immediately once Step 5 On the Monit...

Page 76: ...s to be added Then the UPS alive check function is supported and the RCCMD can check whether the UPS and RCCMD communicate properly The RCCMD client can also receive messages sent by the SNMP card Procedure Step 1 On the RCCMD client add the IP address of the SNMP card that detects heartbeat as shown in Figure 9 1 Step 2 The UPS2000 SNMP card supports both ways of detecting heartbeats If the job c...

Page 77: ...the Server by Using the RCCMD Software Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 69 Figure 9 2 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now as shown in Figure 9 3 ...

Page 78: ...User Manual 9 Protecting the Server by Using the RCCMD Software Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 70 Figure 9 3 Detecting heartbeat manually Figure 9 4 Detecting heartbeat manually and successfully End ...

Page 79: ... the SNMP card through the COM port The BIM is a battery monitoring module that monitors the voltages internal resistances and pole temperatures of batteries 10 2 Connection Settings for the UPS2000 and CIMs Procedure Step 1 Log in to the WebUI of the SNMP card Step 2 On the WebUI choose Config Comm Config CIM Settings and set the number of actually connected CIMs This parameter is not sent to the...

Page 80: ...ings and Number of batteries in a battery string refer to information about the battery strings connected to the UPS The parameters are not sent to the CIMs The SNMP card associates the battery string information with UPSs This is different from the number of battery strings in Config Comm Config CIM Settings 1 Set the Number of battery strings A maximum of four battery strings can be added for ea...

Page 81: ...battery string set on this page Step 7 Verify whether the operation is correct Choose Monitoring Real Time Data Battery String Settings and you can view the data of batteries Choose Monitoring Active alarms and there is no alarm such as CIM number inconsistency BIM communication failure Then the operation is correct If the operation is incorrect check whether each step is performed correctly End 1...

Page 82: ... the UPS runs properly Check that the SNMP card is properly installed Check that the communications cable between the SNMP card and the UPS is intact 2 Web access problems Check that the computer network is normal Check the browser version and the SNMP card IP address that you have entered in the address bar 3 SNMP card problems If the fault persists after the preceding checks replace the SNMP car...

Page 83: ...ade guide Figure 12 1 Upgrade page Procedure Step 1 On the Upgrade page click Browse and select a software upgrade package For versions earlier than UPS2000 V200R001C90 the upgrade package needs to be decompressed Select the file whose file name extension is bin after decompression For UPS2000 V200R001C90 and later versions the upgrade package does not need to be decompressed Select the compressed...

Page 84: ...played as shown in Figure 12 3 Figure 12 3 Upload succeeded page Step 4 Click OK On the Activate Upgrade Package page select the upgrade package under Available Package Version when a package is selected it turns blue Then click Activate to start the upgrade as shown in Figure 12 4 When Upgrade progress reaches 100 and Upgrade Result is Inactive the upgrade is complete as shown in Figure 12 5 Then...

Page 85: ... package page Figure 12 5 Upgrade success page When Upgrade progress is 100 for SNMP card software log in again if the Connection with the UPS failed Check network connectivity and log in again message is displayed If the upgrade fails and the UPS and the SNMP card do not power off click Activate again to restart the upgrade as shown in Figure 12 6 ...

Page 86: ...Ltd 78 Figure 12 6 Upgrade failure scenario 1 If a power failure occurs during the upgrade power on the UPS and SNMP card again After you log in to the WebUI again click Go to Step 3 to perform the upgrade again as shown in Figure 12 7 you can skip Step 1 Step 2 and Step 3 Figure 12 7 Upgrade failure scenario 2 End ...

Page 87: ...the SNMP card over SSH you need to use client software such as PuTTY Security information involved in Secure Shell SSH login is the command line user name and password System accounts are as follows Administrator root Direct login is not supported Log in as enspire and run su to switch to the root account The user name cannot be modified The preset password is Changeme which can be modified Common...

Page 88: ... or special characters _ or space The password must be different from the previous five passwords The password must be different from the user name or its reverse Periodically change the password of the user account A password that has been used for a long time is more likely to be stolen or cracked and the risk increases along with the time of use Change the password at least once half a year 13 ...

Page 89: ...operation Step 4 Run the su command to switch to the root user and enter the root user password as shown in Figure 13 2 Figure 13 2 Switching to the root user Step 5 Run the passwd root command to change the root user password Enter a new password and re enter it as instructed and press Enter Figure 13 3 shows the operation screen Record and keep the password properly If you forgot the password yo...

Page 90: ...RMS SNMP01A SNMP Card User Manual 13 Changing the SSH Access Password Issue 08 2020 01 09 Copyright Huawei Technologies Co Ltd 82 Figure 13 3 Changing the password of the root user End ...

Page 91: ...Acronyms and Abbreviations A AES Advanced Encryption Standard B BIM battery interface module C CIM communication interface module D DES Data Encryption Standard E ESD electrostatic discharge H HTTPS Hypertext Transfer Protocol Secure L LCD liquid crystal display M MD5 message digest algorithm 5 MIB management information base ...

Page 92: ...stem R RJ11 registered jack 11 RJ45 registered jack 45 RMS real time monitor server RS485 Recommended Standard 485 S SHA secure hash algorithm SNMP Simple Network Management Protocol SSH Secure Shell SSL Secure Sockets Layer SOC state of charge SOH state of health T TCP IP Transmission Control Protocol Internet Protocol U UPS uninterruptible power system W WebUI web user interface ...

Reviews: