4 Managing the UPS on the WebUI
Issue 08 (2020-01-09)
Copyright © Huawei Technologies Co., Ltd.
42
Table 4-5
Association between DO status and UPS status
Name Associated
Event
UPS Status
DO Status
DO1
Bypass mode
Bypass mode
NO and COM pins of DO are closed, NC and
COM pins of DO are open.
DO1
Bypass mode
Mains mode
NC and COM pins of DO are closed, NO and
COM pins of DO are open.
Table 4-6
Association between DI status and UPS status
Name Type Associated
Event
DI Status
Execute Event
or Not
DI1
NO
Startup
There is a 12–24 V DC input.
Yes
DI1
NC
Startup
There is a 12–24 V DC input.
No
DI1
NO
Startup
There is no input.
No
DI1
NC
Startup
There is no input.
Yes
CIM Settings
If CIMs are used, set the number of CIMs based on the number of actually connected CIMs,
as shown in
Figure 4-23
CIM settings