55
A
Power Cable Specifications
YJV5 cables are recommended. The conduct working temperature is 90
°
C, and the ambient
temperature is 40
°
C. The following table describes the specifications.
Appendix
For more information, refer to the channels provided on the next page.
Port
Description
Rated
Current (A)
Cable Diameter
(mm²)
Terminal/Bolt
Specifications
Recommended
Torque (N·m)
Power input (L/N)
160
50
DT-M10
27
200
70
DT-M12
47
250
95
DT-M12
47
400
185
DT-M12
47
630
2x185
DT-M12
47
Power input (PE)
160
25
DT-M10
27
200
35
DT-M10
27
250
50
DT-M10
27
400
95
DT-M12
47
630
2x95
DT-M12
47
AC output (L)
< 10
2.5
Cord end terminal
(insertion depth: 8
–12 mm)
1.6
10
≤ I ≤ 40
6
Cord end terminal
(insertion depth: 8
–12 mm)
1.6
40 < I
≤ 63
10
Cord end terminal
(insertion depth: 8
–12 mm)
1.6
AC output (N/PE)
< 10
2.5
OT-M6
4.5
10
≤ I ≤ 40
6
OT-M6
4.5
40 < I
≤ 63
10
OT-M6
4.5
16