![Huawei PDU8000-0125DCV8-BXA006 User Manual Download Page 38](http://html.mh-extra.com/html/huawei/pdu8000-0125dcv8-bxa006/pdu8000-0125dcv8-bxa006_user-manual_167983038.webp)
PDU8000-(0125, 0250, 0400, 0630) DCV8-BXAXXX
BCB Box
User Manual
6 Routine Maintenance
Issue 01 (2019-03-07)
Copyright © Huawei Technologies Co., Ltd.
32
6
Routine Maintenance
Table 6-1
Routine Maintenance
Item
Interv
al
Operation Guide
Reference Standard
Troubleshooting
Connections of
input and output
power cables
Monthl
y
Visual observation.
The cables are not
damaged.
Take measures
depending on the
severity.
The terminals are intact,
secure, and free from
spark signs and rust.
Appearance of
power distribution
components
Quarter
ly
Visual observation.
The appearance is intact.
Take measures
depending on the
severity.
Operating
temperature and
humidity
Quarter
ly
Measure the
temperature and
humidity using a point
thermometer.
Operating temperature:
–5°C to +40°C.
Relative humidity:
5%–95% RH.
Check that the air
conditioner and
dehumidifier in the
equipment room
function properly.
Dust on the surface
of the box
Yearly
Check whether there
is dust.
The white paper that you
use to wipe the
equipment is clean.
If the white paper is
dirty, clean the box.