PDU8000-(0125, 0250, 0400, 0630) DCV8-BXAXXX
BCB Box
User Manual
3 Installation
Issue 01 (2019-03-07)
Copyright © Huawei Technologies Co., Ltd.
13
Terminal Number of
Terminals and
Hole Diameter
Recommended
Cable
Specifications
Recomm
ended
Wiring
Terminal
Recommend
ed Bolt
Specificatio
ns
Reco
mmen
ded
Cable
Color
UPS-
2 x M12
(through-hole)
1 x (2 x
150mm
2
)
150-M12
2 x (M12 x
45)
Black
BAT+
2 x M12
(through-hole)
1 x (2 x
150mm
2
)
150-M12
2 x (M12 x
45)
Red
BAT-
2 x M12
(through-hole)
1 x (2 x
150mm
2
)
150-M12
2 x (M12 x
45)
Black
PE
1 x M12
(through-hole)
1 x 150mm
2
150-M12
M12 x 45
Green-
and-yel
low
The recommended cable specifications are for reference only. Prepare cables based on site requirements.
The following table lists the torque for securing bolts in the BCB box.
Table 3-5
Torque for securing bolts
Bolt Specifications
Torque (N.m)
M6
5
M8
13
M10
27
M12
47
M16
120
3.2.4 Cable Connection Precautions