3 Installation
Issue 01 (2019-03-07)
Copyright © Huawei Technologies Co., Ltd.
11
When the installation environment (such as routing mode and ambient temperature)
changes, prepare cables according to IEC60364-5-52 or local standards.
Use double-insulated polyethylene copper cables. The current-carrying capacity is
calculated based on polyethylene copper cables.
If cables are provided by customers, the cables must be double-insulated and meet 1000
V DC voltage withstanding and current-carrying capacity requirements.
PDU8000-0125DCV8-BXA006 Cables
Table 3-1
Specifications for PDU8000-0125DCV8-BXA006 cables and terminals
Terminal
Number of
Terminals and
Hole Diameter
Recommende
d Cable
Specification
s
Recomme
nded
Wiring
Terminal
Bolt
Specificat
ions
Reco
mmen
ded
Cable
Color
UPS+
1 x M8
(through-hole)
1 x 35mm
2
35-M8
M8 x 25
Red
UPS-
1 x M8
(through-hole)
1 x 35mm
2
35-M8
M8 x 25
Black
BAT+
1 x M8
(through-hole)
1 x 35mm
2
35-M8
M8 x 25
Red
BAT-
1 x M8
(through-hole)
1 x 35mm
2
35-M8
M8 x 25
Black
PE
1 x M6 (rivet nut)
1 x 16mm
2
16-M6
M6 x 16
Green-
and-yel
low
PDU8000-0250DCV8-BXA005 Cables
Table 3-2
Specifications for PDU8000-0250DCV8-BXA005 cables and terminals
Terminal
Number of
Terminals and
Hole Diameter
Recommende
d Cable
Specification
s
Recomme
nded
Wiring
Terminal
Bolt
Specificat
ions
Reco
mmen
ded
Cable
Color
UPS+
1 x M10
(through-hole)
1 x 95mm
2
95-M10
M10 x 40
Red
UPS-
1 x M10
(through-hole)
1 x 95mm
2
95-M10
M10 x 40
Black
BAT+
1 x M10
(through-hole)
1 x 95mm
2
95-M10
M10 x 40
Red
BAT-
1 x M10
1 x 95mm
2
95-M10
M10 x 40
Black