![Huawei PDU8000-0125DCV8-BXA006 User Manual Download Page 18](http://html.mh-extra.com/html/huawei/pdu8000-0125dcv8-bxa006/pdu8000-0125dcv8-bxa006_user-manual_167983018.webp)
PDU8000-(0125, 0250, 0400, 0630) DCV8-BXAXXX
BCB Box
User Manual
3 Installation
Issue 01 (2019-03-07)
Copyright © Huawei Technologies Co., Ltd.
12
Terminal
Number of
Terminals and
Hole Diameter
Recommende
d Cable
Specification
s
Recomme
nded
Wiring
Terminal
Bolt
Specificat
ions
Reco
mmen
ded
Cable
Color
(through-hole)
PE
1 x M8 (rivet nut)
1 x 35mm
2
35-M8
M8 x 25
Green-
and-yel
low
PDU8000-0400DCV8-BXA006 Cables
Table 3-3
Specifications for PDU8000-0400DCV8-BXA006 cables and terminals
Terminal Number of
Terminals and
Hole Diameter
Recommende
d Cable
Specification
s
Recomm
ended
Wiring
Terminal
Recomme
nded Bolt
Specificati
ons
Reco
mmen
ded
Cable
Color
UPS+
1 x M12
(through-hole)
1 x 150mm
2
150-M12
M12 x 45
Red
UPS-
1 x M12
(through-hole)
1 x 150mm
2
150-M12
M12 x 45
Black
BAT+
1 x M12
(through-hole)
1 x 150mm
2
150-M12
M12 x 45
Red
BAT-
1 x M12
(through-hole)
1 x 150mm
2
150-M12
M12 x 45
Black
PE
1 x M10 (rivet nut)
1 x 70mm
2
70-M10
M10 x 25
Green-
and-yel
low
PDU8000-0630DCV8-BXA006 Cables
Table 3-4
Specifications for PDU8000-0630DCV8-BXA006 cables and terminals
Terminal Number of
Terminals and
Hole Diameter
Recommended
Cable
Specifications
Recomm
ended
Wiring
Terminal
Recommend
ed Bolt
Specificatio
ns
Reco
mmen
ded
Cable
Color
UPS+
2 x M12
(through-hole)
1 x (2 x
150mm
2
)
150-M12
2 x (M12 x
45)
Red