R410A Saturation Pressure (Surface Pressure) Table
Temperature
(
°
C)
Saturation
Pressure (MPa)
Temperature
(
°
C)
Saturation
Pressure (MPa)
Temperature
(
°
C)
Saturation
Pressure (MPa)
10
0.99
19
1.31
28
1.69
11
1.02
20
1.35
29
1.74
12
1.05
21
1.39
30
1.79
13
1.09
22
1.43
31
1.84
14
1.12
23
1.47
32
1.89
15
1.16
24
1.51
33
1.94
16
1.19
25
1.56
34
1.99
17
1.23
26
1.60
35
2.05
18
1.27
27
1.65
36
2.10
Oil Trap
2.2
Unit: mm
Pipe
support
Pipe Support
2.3
1. Height of the U-shaped clamp H = Pipe diameter (with thermal insulation foam) – 5 mm.
2. The material for pipe supports and clamps should meet outdoor application requirements.
3. When the pipe is straight, add a support every 1500 mm. When the direction of the pipe is
changed, add a support at the position that is 500 mm away from the changing point.