9
A single outdoor is recommended to be installed against a wall.
Space Requirements for Single Outdoor Unit
If the air baffle is needed, place an air baffle at the air intake side of the outdoor unit based on
the following figure.
Space requirements for maintaining the single wall-mounted outdoor unit
•
The bearing capacity of the support platform is more than 230 kg.
•
Reserve no less than 300 mm from the left or right side of the outdoor unit for
maintenance personnel to walk.
•
Grid structure is recommended to avoid the air exhaust and intake of the smart cooling
product being affected by the guardrail structure.
•
The picture is only for reference, adjust based on the on-site situation if necessary.