6.2 System Power-On
NO TICE
● Power on the LUNA2000 within 24 hours after unpacking. The power-off time
cannot exceed 24 hours during maintenance.
● After turning on the battery switch, power on the inverter. For details about
how to power on the inverter, see the quick guide for the corresponding
inverter model.
NO TE
If no PV module is configured, press the black start button first.
Turn on the DC switch on the battery. After the battery is installed and powered
on for the first time, the ring LED blinks for three circles. Observe the battery
indicator to check the running status.
LED Indicators
Table 6-2 LED indicators
Category
Status (Blinking at Long
Intervals: On for 1s and then
Off for 1s; Blinking at Short
Intervals: On for 0.2s and
then Off for 0.2s)
Description
Running indicator
N/A
Steady
green
Steady green
Operating mode
Blinking
green slowly
Blinking green
slowly
Standby mode
Off
Off
Hibernation mode
Blinking red
fast
N/A
Power control module environment alarm
N/A
Blinking red
fast
Battery expansion module environment
alarm
Steady red
N/A
The power control module is faulty.
N/A
Steady red
The battery expansion module is faulty.
Steady red
Steady red
Faulty
LUNA2000-(5-30)-NHS0
User Manual
6 System Commissioning
Issue 06 (2022-03-01)
Copyright © Huawei Technologies Co., Ltd.
63