Table 4-11 Battery electrical specifications
Item
Specifications
Battery voltage (VRLA
battery)
360–600 V DC
● 12 V batteries (30–50 batteries optional, 0 by
default)
– 40–50 batteries: not derated
– 38–39 batteries: derated to 0.9
– 34–37 batteries: derated to 0.8
– 30–33 batteries: derated to 0.7
● 2 V batteries (180–300 batteries optional, 0 by
default)
– 240–300 batteries: not derated
– 228–239 batteries: derated to 0.9
– 204–227: derated to 0.8
– 180–203: derated to 0.7
NOTE
The number of batteries is 0 by default and needs to be set
based on site requirements. Batteries have no neutral wire,
and an odd number of batteries are supported.
Battery cold start
If a mains outage occurs, batteries can start the UPS to
supply power to loads.
Charger output power
Under rated conditions, the maximum charge power is
15% of module power, and the charge current is
limited to 30 A.
Battery string sharing
Lead-acid battery: Battery string sharing is supported
in a parallel system. No battery is shared by default.
SmartLi 2.0: Battery string sharing is supported. When
multiple UPSs are connected in parallel, the lithium
battery cabinet can be expanded for half a cabinet. No
battery is shared by default.
Charging voltage
(VRLA battery)
● Default equalized charging voltage: 2.35 V/cell
● Default float charging voltage: 2.25 V/cell
Battery type
● VRLA
● SmartLi
NO TICE
The UPS supports the SmartLi. For details about the parameters, see the
SmartLi
User Manual
.
FusionPower6000
Product Description
4 Product Overview