Locate the faulty rPDU based on the alarm information on the monitoring software terminal.
Check that the standby power supply to the rPDU is available.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves, step ladder
Materials: spare rPDU
Documents required: none
Skill requirement: electrician's work permit
Procedure
Step 1
Switch off the circuit breaker of the faulty rPDU in the PDC.
Step 2
Remove all power connectors from the rPDU.
Step 3
Remove the baffle plate from the top of the cabinet using a Phillips screwdriver.
Step 4
Remove the rPDU power cable on the top of the cabinet.
Step 5
Loosen the screws securing the rPDU support at the top and bottom of the rPDU using a
Phillips screwdriver until the rPDU can be removed.
Figure 6-6
Removing screws on the upper and lower sides of the rPDU
Step 6
Lift the faulty rPDU and take it out.
Step 7
Remove the support and screws from the faulty rPDU and install them on a new rPDU.
Step 8
Mount the new rPDU with a support into the cabinet, and tighten the fastening screws of the
rPDU using a Phillips screwdriver.