FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
83
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: spare monitoring rPDU
Documents: none
Skill requirement: electrician's work permit
Procedure
Step 1
Shut down devices powered by the monitoring rPDU.
Step 2
Switch off the rPDU circuit breaker, and unplug devices powered by the rPDU.
Step 3
Remove the monitoring rPDU using a Phillips screwdriver.
Figure 6-5
Removing screws
Step 4
Replace the monitoring rPDU, connect the industrial connectors, and bind the cables using
cable ties.
Step 5
Check that the new rPDU is working properly.
Step 6
Insert device power plugs in the rPDU.
Step 7
after verifying that the new rPDU is working properly.
----End
Follow-up Procedure
Dispose of the removed rPDU that is confirmed faulty.
6.1.6 Replacing a Cabinet rPDU
Prerequisites
An rPDU needs to be replaced.
A spare rPDU of the same model is available and functional.