FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
4 Routine Maintenance
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
51
Device
Operation
Check Standard
Maintenance Guide
Silence/Sound
Alarm
to start or
abort the fire alarm
bell. Reset the key
to
Enable Control
by flipping it
leftward.
started.
Replacing a Fire Alarm
Bell (CE)
Warning
sign
Pull up the reset
button on the
pneumatic switch.
The warning sign
indicator is on.
Replace by following
instructions in
Heat
detector
Heat the heat
detector using a
heating device.
1.
If the temperature
is below the alarm
threshold, the
alarm indicator
blinks once every
6s.
2.
If the temperature
is above the alarm
threshold, the
indicator turns on.
The extinguishant
control panel
generates an
alarm and triggers
the fire alarm bell.
Replace by following
instructions in
Replacing a Heat Detector
(CE)
Smoke
detector
Release smoke
onto the smoke
detector using a
smoke pistol.
1.
If the smoke
density is below
the alarm
threshold, the
alarm indicator
blinks once every
6s.
2.
If the smoke
density is above
the alarm
threshold, the
indicator turns on.
The extinguishant
control panel
generates an
alarm and triggers
the fire alarm bell.
Replace by following
instructions in
Replacing a Smoke Detector
(CE)
Extinguisha
nt abort
button
1.
After the
manual gas
release button is
pressed on the
extinguishant
control panel,
the gas release
countdown
1.
After the
extinguishant
abort button is
pressed, the gas
release
countdown stops.
2.
After the
extinguishant
Replace by following
instructions in