The output signals must meet the following requirements:
l
Current type
–
When moving objects are not detected, the output current should be less than 200 uA.
–
When moving objects are detected, the output current should be greater than 1 mA.
l
Voltage type
–
When moving objects are not detected, the output voltage should be less than 3.3 V.
–
When moving objects are detected, the output voltage should be greater than 5 V.
l
Dry contact point type
–
When moving objects are detected, the sensor should be disconnected.
–
When moving objects are detected, the sensor should be connected.