Silkscreen
Function
Setting
SW12A,
SW12B,
SW24A,
SW24B
Thirty-two bits for Boolean
signal input
l
Bits 1-8 of the DIP switch SW12A
correspond to input signals 1-8.
l
Bits 1-8 of the DIP switch SW12B
correspond to input signals 9-16.
l
Bits 1-8 of the DIP switch SW24A
correspond to input signals 17-24.
l
Bits 1-8 of the DIP switch SW24B
correspond to input signals 25-32.
l
When a bit is set to ON, it represents high-
level alarms.
l
When a bit is set to OFF, it represents low-
level alarms or is not used.
NOTE
The configurations described in this document apply only to the sensors provided by Huawei. For sensors
of other types, see their respective instructions.
2.4 Communication Ports on the EMU
The EMU provides the RS485 and RS232 ports for the communication between the EMU and
the BTS/NodeB.
2.4.1 RS485 Serial Port
This describes the RS485 serial port on the EMU. Two RS485 serial ports are used in active/
standby mode for the communication between the EMU and the BTS/NodeB. The RS485 serial
port is suitable for a dedicated serial port that has a DB-9 male connector.
For the position of the RS485 serial port on the EMU, see
shows the pins of the RS485 serial port socket.
Figure 2-6
Pins of the RS485 serial port socket
EMU
User Guide
2 Overview of the EMU
Issue 13 (2009-12-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2-7