Item
Interval
Operating Instruction
Reference Standard
Cleaning the
equipment
room
Every two
months
Check whether cabinets,
equipment housing,
equipment interior, tables,
floor, doors, and windows
are clean.
All the items to be checked
are clean.
3.2 Power Supply and Grounding System Maintenance
Items of the NodeB
This provides the maintenance items, maintenance intervals, operation instructions, and
reference standards of the NodeB power supply and grounding system.
lists the routine maintenance items for the power supply and the grounding system
of the NodeB.
Table 3-2
Maintenance items of the power supply and grounding system of the NodeB
Item
Interval
Operating
Instruction
Reference Standard
Checking power
cables
Monthly
Check the connections
of power cables
carefully.
The power cables are not
aging, and there is no
corrosion on the
connection points.
Checking the
voltage
Monthly
Measure the voltage of
the power supply by
using a multimeter.
The voltage is within
standard range.
Checking PGND
cables
Monthly
Check whether the
PGND cable and
grounding bar are
connected properly.
The connections of the
PGND cable are sound. It
is not aging. The
connection points are
sound with no corrosion
on them.
Earth resistance
Monthly
Measure the earth
resistance by using an
electric earth resistance
tester and keep a record.
The grounding resistance
of the cabinet is smaller
than 10 ohms.
Checking the
storage batteries
Yearly
Check the storage
batteries and rectifiers
every year.
The battery capacity is
within the normal range
and the batteries are
correctly connected. The
performance parameters
of rectifiers are normal.
BTS3900 WCDMA
Site Maintenance Guide
3 Hardware Items of BTS3900 Routine Maintenance
Issue 07 (2009-08-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3-3