Procedure
Step 1
Strip a part of the insulation to expose the cable conductor with a length of L, as shown in
. The recommended values of L are listed in
.
NOTICE
l
When you strip a power cable, do not damage the conductor of the cable.
l
If the bare crimping terminal is not provided by Huawei, you can adjust the value of L as
required.
Figure 5-7
Stripping a power cable (JG terminal)
Table 5-2
Mapping between the cross-sectional area of the conductor and the value of L
Cross-Sectional Area of Conductor
(mm
2
(in.
2
))
Value of L (mm(in.))
16 (0.025)
13 (0.51)
25 (0.039)
14 (0.55)
35 (0.054)
16 (0.63)
50 (0.077)
16 (0.63)
Step 2
Put the heat shrink tubing onto the bare crimping terminal, as shown in
.
R250D
Hardware Installation and Maintenance Guide
5 Appendix
Issue 01 (2016-09-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
27