6.9 For Serviceman
OPERATION PARAMETER
#00
OPERATE MODE
COOL
ADDRESS
SV1 STATE
ON
The power consumption parameter is optional. If some parameter
is not be activated in the system, the parameter will show "--"
The heat pump capacity is for reference only, not used to judge
the ability of the unit. The accuracy of sensor is ±1
℃
. The flow
rates parameters are calculated according to the pump running
parameters,the deviation is different at different flow rates,the
maximum of deviation is 15%.The flow parameters are calculated
according to the electrical parameters of the pump operation.
The operating voltage is different and the deviation is different.
The display value is 0 when the voltage is less than 198V.
INFORMATION
i
6.9.1 About For Serviceman
FOR SERVICEMAN is used for installater and service
engineer.
Setting the function of equipment.
Setting the parameters.
6.9.2 How To Go To For Serviceman
Go to ''MENU'' > ''FOR SERVICEMAN''. Press ''OK''.
ONLINE UNITS NUMBER
1
SV2 STATE
OFF
SV3 STATE
OFF
PUMP_I
ON
1/9
OPERATION PARAMETER
#00
PUMP_C
OFF
ADDRESS
PUMP_S
OFF
PUMP_O
OFF
PUMP_D
OFF
PIPE BACKUP HEATER
OFF
TANK BACKUP HEATER
ON
2/9
OPERATION PARAMETER
#00
T1 LEAVING WATER TEMP. 35°C
ADDRESS
WATER FLOW
1.72m
3
/h
GAS BOILER
OFF
HEAT PUMP CAPACTIY 11.52kW
POWER CONSUM
1000kWh
Ta ROOM TEMP.
25°C
3/9
OPERATION PARAMETER
#00
Tw2 CIRCUIT2 WATER TEMP. 35°C
ADDRESS
TIS’ C1 CLI. CURVE TEMP. 35°C
T5 WATER TANK TEMP.
53°C
TIS2’ C2 CLI. CURVE TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
TW_I PLATE W-INLET TEMP. 30°C
4/9
OPERATION PARAMETER
#00
Tbt2 BUFFERTANK_LOW TEMP. 35°C
ADDRESS
IDU SOFTWARE
01-09-2019V01
Tbt1 BUFFERTANK_UP TEMP. 35°C
5/9
OPERATION PARAMETER
#00-
COMP.CURRENT
12A
ADDRESS
COMP.FREQENCY
24Hz
ODU MODEL
6kW
COMP.RUN TIME
54 MIN
COMP.TOTAL RUN TIME 1000Hrs
EXPANSION VALVE
200P
6/9
OPERATION PARAMETER
#00
IDU TARGET FREQUENCY 46Hz
ADDRESS
FREQUENCY LIMITED TYPE 5
FAN SPEED
600R/MIN
SUPPLY VOLTAGE
230V
DC GENERATRIX VOLTAGE 420V
DC GENERATRIX CURRENT 18A
7/9
OPERATION PARAMETER
#00
TW_I PLATE W-INLET TEMP. 30°C
ADDRESS
T2 PLATE F-OUT TEMP.
35°C
TW_O PLATE W-OUTLET TEMP. 35°C
T2B PLATE F-IN TEMP.
35°C
Th COMP. SUCTION TEMP. 5°C
Tp COMP. DISCHARGE TEMP. 75°C
8/9
OPERATION PARAMETER
#00
T4 OUTDOOR AIR TEMP.
5°C
ADDRESS
TF MODULE TEMP.
55°C
T3 OUTDOOR EXCHARGE TEMP. 5°C
P1 COMP. PRESSURE
2300kPa
ODU SOFTWARE 01-09-2018V01
HMI SOFTWARE 01-09-2018V01
9/9
Tsolar
25°C
Please input password:
2
3 4
ENTER
OK
FOR SERVICEMAN
ADJUST
Summary of Contents for ECO-THERMAL
Page 2: ......
Page 3: ...C O N T R O L C A B L E A D O ECO THERMAL ESPA OL Manual de Usuario HTW KJRH120HBMKOE...
Page 31: ......
Page 32: ...W I R E D C O N T R O L L E R ECO THERMAL ENGLISH Owner s manual HTW KJRH120HBMKOE...
Page 60: ......
Page 61: ...C O M M A N D E D E C B L A G E ECO THERMAL FRAN AIS Manuel de l Utilisateur HTW KJRH120HBMKOE...
Page 89: ...27...
Page 90: ...C O M A N D O C O M F I O ECO THERMAL PORTUGU S Manual do Utilizador HTW KJRH120HBMKOE...
Page 118: ......
Page 119: ...C O N T R O L L O A F I L O ECO THERMAL ITALIANO Manuale Utente HTW KJRH120HBMKOE...
Page 147: ...27...
Page 148: ...28...
Page 149: ...29...
Page 150: ...30...
Page 151: ...31...