LP-719 Rev. 000 Rel. 000 Date 6.25.20
65
M
enu
Sub
-M
enu
Par
amet
er
Description
Value
Default Setting
6
2
2
Slope of Outdoor Reset Curve
0.2 -0.8
0.6
(low temperature)
0.4 - 3.5
1.3
(high temperature)
See graph and description of Parameter 422.
6
2
3
Parallel Shift of Reset Curve
-12 - +12 (when 4.2.0 = 0)
0
-25 - +25 (when 4.2.0 = 1)
See description of Parameter 423.
6
2
4
Room Sensor Influence
0 - 20
2
if Parameter 4.2.0 = 0
4
if Parameter 4.2.0 = 1
Adjusts the influence of room temperature on target boiler temperature - a higher setting causes a greater increase to the
boiler target temperature as the indoor temperature drops below room setpoint.
Only applicable when using an optional
HTP Room Sensor and when 6.2.1 = 2 or 4.
6
2
5
MAXIMUM temperature setting
86 - 179 °F
179
if Parameter 6.2.0 = 1
68 - 122 °F
120
if Parameter 6.2.0 = 0
6.2.5 sets the allowable boiler operating temperature range for Zone 3 heating, limiting Automatic Temperature Control and
manual adjustments from the User Menu.
6
2
6
MINIMUM temperature setting
86 - 179 °F
120
if Parameter 6.2.0 = 1
68 - 122 °F
80
if Parameter 6.2.0 = 0
6.2.6 sets the allowable boiler operating temperature range for Zone 3 heating, limiting Automatic Temperature Control and
manual adjustments from the User Menu.
6
3 DIAGNOSTICS
6
3
0
S/W function activation
0 = OFF, 1 = ON
0
Only applicable when using an
HTP room sensor
6
3
1
S/W temperature threshold
50 - 86 °F
68
6
3
4
S/W delay time
0 - 300 minutes
60
6
7 ZONE 3 REGULATION PARAMETERS
6
7
5
Auto Boost
0 = OFF, 1 = ON
0
See description of Parameter
475.
8 SERVICE PARAMETERS
8
0 BOILER STATISTICS-1 - Read Only
8
0
0
3 way valve cycles No. (n x10)
8
0
1
Boiler Pump On Hours (h x10)
8
0
2
Boiler pump cycles No. (n x10)
8
0
3
Boiler Power On Time (h x10)
8
0
4
Fan On Hours (h x10)
8
0
5
Number of fan cycles (n x10)
8
0
6
CH number of flame detections (n x10)
8
0
7
DHW number of flame detections (n x10)
8
1 BOILER STATISTICS-2 - Read Only
8
1
0
CH Burner On Hours (h x10)
8
1
1
DHW Burner On Hours (h x10)
8
1
2
Number Of Flame Faults (n x10)
8
1
3
Number Of Ignition Cycles (n x10)
8
1
4
Average CH Cycle Length (min)
8
1
6
Number of times the Priority Timer (2.10.4) has elapsed, switching priority from DHW to CH (or vice versa).
8
2 BOILER CURRENT STATUS - Read Only
8
2
1
Fan Status
0 = OFF, 1 = ON
8
2
2
Fan Speed RPM
8
2
3
Boiler Pump Status
0 = OFF, 1 or 2 = ON
8
2
4
3 Way Valve Position
0 = DHW, 1 = Central Heating
8
2
5
DHW Flow Rate (in US gpm)
Not applicable to Non-Combi
models
8
2
6
APS Status
0 = Open, 1 = Closed
8
2
8
Gas Power (kW)
8
3 BOILER CURRENT TEMPERATURES - Read Only
8
3
0
CH Supply Setpoint (in °F)