lp-585 Rev. 000 Rel. 001 Date 9.10.18

9

centralized to the solar tank and domestic piping system and near 

the solar collectors as possible. Also, locate the tank in as warm a 

location as possible, away from areas which would subject the drain 

back tank reservoir to freezing temperatures. All piping should be 

insulated to protect against freezing and minimize heat loss. 
Additionally, the drain back tank, solar water heater, and all 

related solar system components should be installed with plenty 

of clearance for inspection and service. If minimum clearances are 

not met, it may not be possible to service the solar system without 

removing components from installation locations.
The drain back tank should also be installed in a place where T&P 

discharge or a leak will not result in damage to the surrounding area. 

Install a 2” high drain pan with a minimum of ¾” drain line to prevent 

water damage if leakage should occur. See Figure 3.

Figure 3 - Recommended Service Clearances

Filled hot water storage and drain back tanks are very heavy, and 

should be located in areas that can structurally support such 

weight. Failure to properly locate water storage tanks could result 

in property damage, personal injury, or death.

D. Specifications and Dimensions

Figure 4 - Drain Back Tank without Heat Exchanger Specifications and 

Dimensions

This tank must be installed upright in the vertical position as 

described in this manual. DO NOT attempt to install this tank in any 

other orientation. Doing so will result in improper tank operation 

and property damage, and could result in serious personal injury 

or death.

Part 5 - Piping

The design and installation of the solar water heating system should 

be done by qualified individuals. It is important that good design 

and installation practices be followed to assure that your system will 

operate properly. Failure to follow installation guidelines for you solar 

water heating system could cause component failure and possible 

safety issues.

A. Potable Water Piping

It is very important that you do the potable piping before you pipe 

into your solar system. Failure to do so may damage your water 

heater.
Do not introduce HTF into any fittings on the heater except those 

clearly marked for that purpose.

It is mandatory that all plumbing be done in accordance with local 

and state codes or warranty will be void. It is also necessary to use 

both thread tape and pipe dope on all mechanical connections. The 

potable water piping is located on the side of your solar water heater 

and marked Hot and Cold. It is recommended that unions or flexible 

copper connectors be used so heater can be easily serviced. Install a 

shut-off valve on the cold feed near the solar water heater to isolate 

the tank for future service.
Provide clear access to the storage tank, pump, expansion tank, mixing 

valve, time clock and other key components. The components on the 

potable side of the system may require future service or maintenance, 

All drain back tanks eventually leak. Locate the tank where any 

leakage from the relief valve, related piping, tank, or connections 

will not result in damage to surrounding areas or lower floors 

of the building. Any drain back tank should be installed in such 

a manner that if it should leak the resulting flow of water will 

not cause damage to the area in which it is installed. National 

Plumbing codes require a drain pan for any water heater 

installation. This drain pan should be sized with a maximum depth 

of 2”, and a minimum diameter 2” greater than the diameter of 

the water heater. The drain pan should empty into an open drain 

line. This drain line should be 3/4” ID minimum, piped to an open 

drain. Leakage damages ARE NOT covered by warranty. Failure to 

install a drain pan is the sole responsibility of the owner and/or 

installer. Reference UPC 2000 (Uniform Plumbing Code) Section 

510 - Protection from Damage or IPC 200 (International Plumbing 

code) Section 504 - Safety Devices. Leakage damages ARE NOT 

covered by warranty.

In addition, water leak detection devices and automatic water 

shutoff valves are readily available at plumbing supply houses. IT 

IS HIGHLY RECOMMENDED BY THE MANUFACTURER TO INSTALL 

WATER LEAK DETECTION DEVICES AND AUTOMATIC SHUTOFF 

VALVES IN ANY DRAIN BACK TANK INSTALLATION WHERE A 

LEAKAGE OF WATER COULD RESULT IN PROPERTY DAMAGES. 

Summary of Contents for Drain Back

Page 1: ...ication does not imply endorsement or warranty of this product by the SRCC This manual must only be used by a qualified installer service technician Read all instructions in this manual before installing Perform steps in the given order Failure to do so could result in substantial property damage severe personal injury or death HTP reserves the right to make product changes or updates without noti...

Page 2: ... where they differ from the furnished instructions Always use the latest edition of codes Additional publications which should guide the installer include Local state provincial and national codes laws regulations and ordinances Solar Water Heating System Design and Installation Guidelines SRCC OG 300 available from Solar Rating Certification Corporation 400 High Point Drive Suite 400 Cocoa FL 329...

Page 3: ...C Start Up Procedure 15 Part 8 Service Maintenance Procedures 15 A Shutdown Procedures 16 B Draining the Drain Back Reservoir 16 C Routine Maintenance 16 D Vacation Shutdown Procedure 16 E Estimated Life of Components 16 F Temperature and Pressure Relief Valve 16 Part 9 Troubleshooting 16 A Leaks 16 B Other Problems 16 C Operating Suggestions for the User 16 Part 10 System Parts Listing 17 A Estim...

Page 4: ...erant leaks Auto body shops Paint or varnish removers Plastic manufacturing plants Hydrochloric or Muriatic acid Furniture refinishing areas and establishments Cements and glues New building construction Antistatic fabric softeners used in clothes dryers Remodeling areas Chlorine type bleaches laundry detergents and cleaning solvents Garages and workshops Adhesives used to fasten building products...

Page 5: ...d in copper to an appropriate drainage location will provide sufficient expansion protection This pressure relief valve and drain outlet pipe must never be sealed or blocked The pressure relief valve is intended to be operated for safety purposes only NOTE Supply and return connections to the collector must use eccentric fittings or a fitting arrangement that allows full draining of header pipes T...

Page 6: ...al heat output A deviation of up to 15o from due south is acceptable and will have minimal effect on heat output D Mounting Methods A B Sloped Roof C Flat Roof D Facade Figure 1 Suggested Solar Collector Mounting Designs 2 Collector Angle Tilt It is common for collectors to be installed at an angle that corresponds to the installation latitude While adhering to this guideline an angle of latitude ...

Page 7: ... hose clamp Wire nuts used to connect the sensor and low voltagewiringshallbeallplastic sealedwithsiliconeandthoroughly wrapped in electrician s tape The low voltage wiring used to connect the sensors to the controller should be a minimum 18 AWG The wiring should be bare or tinned copper two conductor PVC insulated with a PVC UV rated gray jacket suitable for exterior use Use Eastman Wire Cable no...

Page 8: ...ted thermostatic mixing valve IS REQUIRED PER SRCC OG 300 B Tools and Materials The following is a minimum list of basic required tools Other plumbing components will be field supplied according to installation needs COLDWEATHER HANDLING If the water heater has been stored in a very cold location BELOW 0o F before installation handle with care Failure to do so could result in damage to the water h...

Page 9: ...ng before you pipe into your solar system Failure to do so may damage your water heater Do not introduce HTF into any fittings on the heater except those clearly marked for that purpose It is mandatory that all plumbing be done in accordance with local and state codes or warranty will be void It is also necessary to use both thread tape and pipe dope on all mechanical connections The potable water...

Page 10: ...ck systems When making a connection to the heat exchanger use Teflon Tape and joint compound to prevent leaks Do not apply heat directly to the heat exchanger thread connection when sweating fittings Line pressure and temperature gauge shall be installed in the collector supply and return lines to allow for a simple diagnostic check of proper system operation On a sunny day the hot water return li...

Page 11: ...ge to an acceptable and safe temperature This also increases the amount of hot water drawn from the solar water heater by not allowing incoming cold water to fully temper the hot water stored inside the tank To help prevent injury due to scalding it is recommended that the mixing valve be set at 120oF Ball Valve for cold water shut off Valve 24 The cold water shut off valve should be used in the e...

Page 12: ...d to supply power to the pump control combo H Installing the Drain Back Tank Sight Tube IMPORTANT NOTE A sight tube has been included with the solar drain back tank The sight tube allows service technicians installers and users to quickly determine proper drain back system drainage and solar system heat transfer fluid level It is extremely important that this sight tube be installed BEFORE filling...

Page 13: ... water and maximum tank temperature Normal solar control settings may be between 120o and 160o Do not exceed 160o on the solar control setting 4 A solar rated mixing valve is recommended if the domestic hot water setting is above 120oF A standard mixing valve generally cannot deliver the temperature protection range at which a solar system operates 5 A minimum of 12 diameters of straight pipe must...

Page 14: ...nd maximum tank temperature Normal solar control settings may be between 120o and 160o Do not exceed 160o on the solar control setting 4 A solar rated mixing valve is recommended if the domestic hot water setting is above 120oF A standard mixing valve generally cannot deliver the temperature protection range at which a solar system operates 5 A minimum of 12 diameters of straight pipe must be inst...

Page 15: ...reeze protection Please refer to glycol manufacturer s specifications about the temperature ranges the liquid can withstand Only food grade polypropylene glycol FDA rated as GRAS should be used NOTE HTP DOES NOT WARRANT THE SOLAR WATER HEATER SOLAR COLLECTOR OR ANY COMPONENTS AGAINST FREEZE RELATED DAMAGE Part 7 Start Up Preparation DO NOT MOVE ON TO THESE STEPS UNTIL THE ENTIRE SOLAR SYSTEM INCLU...

Page 16: ...ms may have a greater temperature difference The storage tank should be flushed to prevent scale build up on an annual or bi annual basis following the manufacturer s recommendations Following installation of the T P Relief Valve the valve lever MUST be operated AT LEAST ONCE AYEAR by the water heater owner to ensure that waterways are clear Certain naturally occurring mineral deposits may adhere ...

Page 17: ...ion when using hot water to avoid scald injury Consult codes for conformance Failure to follow the instructions in this warning statement could result in serious personal injury or death from scalds Be sure to disconnect electrical power before performing service Failure to do so could result in electrical shock property damage serious personal injury or death If draining of the water heater is ne...

Page 18: ...lp 585 Rev 000 Rel 001 Date 9 10 18 18 ...

Page 19: ...lp 585 Rev 000 Rel 001 Date 9 10 18 19 ...

Page 20: ...oily layer burnt odor or any heavy sludge in the fluid may indicate the need for replacement TESTING THE FLUID pH LEVEL Control of pH between 8 and 10 is important to minimize corrosion and glycol degradation Using narrow range pH paper such as pHydrion Control paper with a 7 2 to 8 8 pH range is an easy and reliable way to read your pH level A pH tester can also measure alkalinity or acidity and ...

Page 21: ...odel Number Solar Collector Company Model of Collectors 30004176 30004189 DB 80 40 GB DB 80 40 EB AET AE 40 MSC 40 1 HTP SS 40 SS 40 FP 30004175 30004188 30004173 30004186 DB 80 64 GB DB 80 64 EB DB 119 64 GB DB 119 64 EB AET AE 32 MSC 32 2 HTP SS 32 SS 32 FP 30004174 30004187 30004172 30004185 DB 80 80 GB DB 80 80 EB DB 119 80 GB DB 119 80 EB AET AE 40 MSC 40 2 HTP SS 40 SS 40 FP 30004171 3000418...

Page 22: ...lp 585 Rev 000 Rel 001 Date 9 10 18 22 This Page Left Intentionally Blank ...

Page 23: ...lp 585 Rev 000 Rel 001 Date 9 10 18 23 ...

Page 24: ...lp 585 Rev 000 Rel 001 Date 9 10 18 24 This Page Left Intentionally Blank ...

Page 25: ... ASME installed with the drain back tank assembly in accordance with federal state and local codes 2 Maintain the drain back tank in accordance with the maintenance procedure listed in the manufacturer s provided instructions Preven tive maintenance can help avoid any unnecessary breakdown of the drain back tank and keep the system running at optimum efficiency 3 Maintain all related system compon...

Page 26: ...S Except when specifically prohibited by the applicable state law the Owner and not the Manufacturer shall be liable for and shall pay for all charges for labor or other expenses incurred in the removal repair or replacement of the drain back tank or any component part s claimed to be defective or any expense incurred to remedy any defect in the product Such charges include but are not necessarily...

Page 27: ...tive Distributor Dealer Please insert contact details Customer Installation Record Form The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim After reading the important notes at the bottom of the page please also sign this document Customer s Name Date of Installation Installation Address Product Name Serial Number s Co...

Reviews: