background image

lp-585 Rev. 000 Rel. 001 Date 9.10.18

6

solar hot water heaters provide a backup when solar contribution is 

limited due to adverse weather conditions.

Do not introduce HTF into any fittings on the heater except those 

clearly marked for that purpose.

B. System Design

System design should be completed prior to installation. Solar 

collectors need to be installed correctly to ensure high efficiency and, 

most importantly, safe and reliable operation. Please seek professional 

advice for the design and installation of your solar heating system.

NOTE:

 Only authorized licensed contractors are permitted to install 

the solar collector.

C. Solar Collector Installation

NOTE:

 These solar collector instructions are general in nature. 

Reference the solar collector manufacturer’s instructions for more 

specific and detailed installation information.
The solar collector installation contractor shall obtain all required 

permits and approvals when installing the solar system. The installation 

shall conform to all federal, state and local regulations governing 

solar water heating system installations. The contractor shall adhere 

to sound building safety and trade practices. Special consideration 

must be given to building code requirements for the penetration of 

structural members and fire rated assemblies.

All persons working on roofs should have completed a fall safety 

course and must be properly outfitted with appropriate safety 

equipment. Failure to follow this information could result in property 

damage, severe personal injury, or death.

Before installation, the contractor shall inspect the condition of 

the roof and notify the homeowner of any existing roof damage or 

necessary repairs. The most important structural consideration is to 

securely anchor the solar collector and solar strut mounting hardware 

to the structural members of the roof with stainless steel hanger or lag 

bolts. Consult with the collector manufacturer installation manual for 

proper guidelines in your application.

Solar collectors should be covered at all times until installation is 

complete. Failure to follow this information could result in severe 

personal injury or death.

Preserving the integrity of the roof membrane is the most important 

roofing consideration. Ensure that all roof penetrations required to 

plumb and mount the solar collector are properly flashed and sealed 

in accordance with standard roofing practices. The recommended 

elastomer for sealing roof penetrations is Tremco “POLYroof”.

D. Collector Angle, Plane, and Direction

1. Collector Direction

The collector should face the equator. In the northern hemisphere, 

this is due south, and in the southern hemisphere, due north. Facing 

the collector in the correct direction and angle is important to ensure 

optimal heat output. A deviation of up to 15

o

 from due south is 

acceptable, and will have minimal effect on heat output.

Figure 1 - Suggested Solar Collector Mounting Designs

2. Collector Angle (Tilt)

It is common for collectors to be installed at an angle that corresponds 

to the installation latitude. While adhering to this guideline, an angle of 

la/- 10

o

 is acceptable, and will not greatly reduce solar output. 

The solar collector should be installed at an angle between 20 – 80

o

 to 

ensure optimal operation.
For year-round domestic hot water, the collector should be tilted to 

an angle of equal to the latitude of the installation site. Add 15

o

 to 

3. Collector Plane (Horizontal or Vertical)

The collector could be installed vertically, but may be installed at an 

angle, such as sideways on a pitched roof. It is not recommended 

to install a drain back system in the horizontal or landscape style. 

In vertical installations, collectors may be installed with 1/4” pitch 

towards the supply port to facilitate the drain back process.

E. Collector Piping

Collector piping in drain back systems may be constructed of 

copper and brass fittings, or PEX.

Systems Piped in Copper

To avoid leaks and fluid loss, copper and brass ground joint unions 

should be used to join the collectors. Use only lead-free solder. 

Engelhard Silvabrite 100 or equivalent is the required soldering 

material. Use of 50/50 lead solder is expressly prohibited. Use of 

galvanized steel, CPVC, PVC or any other nonrated plastic pipe is 

prohibited.

Systems Piped in PEX

•  The PEX shall not be exposed to sunlight.

•  Drain back systems employing PEX shall be non-pressurized 

(capped at atmospheric on the day of installation) or the 

system shall be vented to the atmosphere.

•  At the inlet and outlet of the collector(s), a length of 

uninsulated copper tube of no less than ¾” nominal 

diameter shall be used for a distance of no less than three 

feet before the conversion to PEX for the return line is made.

•  Connections in the PEX piping runs to and from the collectors 

shall use only those fittings supplied and/or approved by 

the PEX manufacturer for potable water piping.

•  The systems shall have a pressure-only relief valve installed 

at the drain back tank location or the tank shall be vented to 

the atmosphere. The pressure rating for this valve shall be 

no less than 25 psi and no more than 50 psi.

Never use dielectric unions or galvanized steel fittings in the 

collector loop. Doing so will lead to corrosion, property damage, 

and possible early water heater failure. Such damage IS NOT 

covered by warranty. Use only copper and brass fittings.

the latitude to optimize for winter performance (space heating). 

Subtract 15

o

 from the latitude to optimize for summer performance 

(indirect pool heating).
Given the formula above, a solar collector installed at 30

o

N latitude 

should face due south at an angle of 45

o

 for wintertime advantage, 

and 15

o

 for summertime heating.

Summary of Contents for Drain Back

Page 1: ...ication does not imply endorsement or warranty of this product by the SRCC This manual must only be used by a qualified installer service technician Read all instructions in this manual before installing Perform steps in the given order Failure to do so could result in substantial property damage severe personal injury or death HTP reserves the right to make product changes or updates without noti...

Page 2: ... where they differ from the furnished instructions Always use the latest edition of codes Additional publications which should guide the installer include Local state provincial and national codes laws regulations and ordinances Solar Water Heating System Design and Installation Guidelines SRCC OG 300 available from Solar Rating Certification Corporation 400 High Point Drive Suite 400 Cocoa FL 329...

Page 3: ...C Start Up Procedure 15 Part 8 Service Maintenance Procedures 15 A Shutdown Procedures 16 B Draining the Drain Back Reservoir 16 C Routine Maintenance 16 D Vacation Shutdown Procedure 16 E Estimated Life of Components 16 F Temperature and Pressure Relief Valve 16 Part 9 Troubleshooting 16 A Leaks 16 B Other Problems 16 C Operating Suggestions for the User 16 Part 10 System Parts Listing 17 A Estim...

Page 4: ...erant leaks Auto body shops Paint or varnish removers Plastic manufacturing plants Hydrochloric or Muriatic acid Furniture refinishing areas and establishments Cements and glues New building construction Antistatic fabric softeners used in clothes dryers Remodeling areas Chlorine type bleaches laundry detergents and cleaning solvents Garages and workshops Adhesives used to fasten building products...

Page 5: ...d in copper to an appropriate drainage location will provide sufficient expansion protection This pressure relief valve and drain outlet pipe must never be sealed or blocked The pressure relief valve is intended to be operated for safety purposes only NOTE Supply and return connections to the collector must use eccentric fittings or a fitting arrangement that allows full draining of header pipes T...

Page 6: ...al heat output A deviation of up to 15o from due south is acceptable and will have minimal effect on heat output D Mounting Methods A B Sloped Roof C Flat Roof D Facade Figure 1 Suggested Solar Collector Mounting Designs 2 Collector Angle Tilt It is common for collectors to be installed at an angle that corresponds to the installation latitude While adhering to this guideline an angle of latitude ...

Page 7: ... hose clamp Wire nuts used to connect the sensor and low voltagewiringshallbeallplastic sealedwithsiliconeandthoroughly wrapped in electrician s tape The low voltage wiring used to connect the sensors to the controller should be a minimum 18 AWG The wiring should be bare or tinned copper two conductor PVC insulated with a PVC UV rated gray jacket suitable for exterior use Use Eastman Wire Cable no...

Page 8: ...ted thermostatic mixing valve IS REQUIRED PER SRCC OG 300 B Tools and Materials The following is a minimum list of basic required tools Other plumbing components will be field supplied according to installation needs COLDWEATHER HANDLING If the water heater has been stored in a very cold location BELOW 0o F before installation handle with care Failure to do so could result in damage to the water h...

Page 9: ...ng before you pipe into your solar system Failure to do so may damage your water heater Do not introduce HTF into any fittings on the heater except those clearly marked for that purpose It is mandatory that all plumbing be done in accordance with local and state codes or warranty will be void It is also necessary to use both thread tape and pipe dope on all mechanical connections The potable water...

Page 10: ...ck systems When making a connection to the heat exchanger use Teflon Tape and joint compound to prevent leaks Do not apply heat directly to the heat exchanger thread connection when sweating fittings Line pressure and temperature gauge shall be installed in the collector supply and return lines to allow for a simple diagnostic check of proper system operation On a sunny day the hot water return li...

Page 11: ...ge to an acceptable and safe temperature This also increases the amount of hot water drawn from the solar water heater by not allowing incoming cold water to fully temper the hot water stored inside the tank To help prevent injury due to scalding it is recommended that the mixing valve be set at 120oF Ball Valve for cold water shut off Valve 24 The cold water shut off valve should be used in the e...

Page 12: ...d to supply power to the pump control combo H Installing the Drain Back Tank Sight Tube IMPORTANT NOTE A sight tube has been included with the solar drain back tank The sight tube allows service technicians installers and users to quickly determine proper drain back system drainage and solar system heat transfer fluid level It is extremely important that this sight tube be installed BEFORE filling...

Page 13: ... water and maximum tank temperature Normal solar control settings may be between 120o and 160o Do not exceed 160o on the solar control setting 4 A solar rated mixing valve is recommended if the domestic hot water setting is above 120oF A standard mixing valve generally cannot deliver the temperature protection range at which a solar system operates 5 A minimum of 12 diameters of straight pipe must...

Page 14: ...nd maximum tank temperature Normal solar control settings may be between 120o and 160o Do not exceed 160o on the solar control setting 4 A solar rated mixing valve is recommended if the domestic hot water setting is above 120oF A standard mixing valve generally cannot deliver the temperature protection range at which a solar system operates 5 A minimum of 12 diameters of straight pipe must be inst...

Page 15: ...reeze protection Please refer to glycol manufacturer s specifications about the temperature ranges the liquid can withstand Only food grade polypropylene glycol FDA rated as GRAS should be used NOTE HTP DOES NOT WARRANT THE SOLAR WATER HEATER SOLAR COLLECTOR OR ANY COMPONENTS AGAINST FREEZE RELATED DAMAGE Part 7 Start Up Preparation DO NOT MOVE ON TO THESE STEPS UNTIL THE ENTIRE SOLAR SYSTEM INCLU...

Page 16: ...ms may have a greater temperature difference The storage tank should be flushed to prevent scale build up on an annual or bi annual basis following the manufacturer s recommendations Following installation of the T P Relief Valve the valve lever MUST be operated AT LEAST ONCE AYEAR by the water heater owner to ensure that waterways are clear Certain naturally occurring mineral deposits may adhere ...

Page 17: ...ion when using hot water to avoid scald injury Consult codes for conformance Failure to follow the instructions in this warning statement could result in serious personal injury or death from scalds Be sure to disconnect electrical power before performing service Failure to do so could result in electrical shock property damage serious personal injury or death If draining of the water heater is ne...

Page 18: ...lp 585 Rev 000 Rel 001 Date 9 10 18 18 ...

Page 19: ...lp 585 Rev 000 Rel 001 Date 9 10 18 19 ...

Page 20: ...oily layer burnt odor or any heavy sludge in the fluid may indicate the need for replacement TESTING THE FLUID pH LEVEL Control of pH between 8 and 10 is important to minimize corrosion and glycol degradation Using narrow range pH paper such as pHydrion Control paper with a 7 2 to 8 8 pH range is an easy and reliable way to read your pH level A pH tester can also measure alkalinity or acidity and ...

Page 21: ...odel Number Solar Collector Company Model of Collectors 30004176 30004189 DB 80 40 GB DB 80 40 EB AET AE 40 MSC 40 1 HTP SS 40 SS 40 FP 30004175 30004188 30004173 30004186 DB 80 64 GB DB 80 64 EB DB 119 64 GB DB 119 64 EB AET AE 32 MSC 32 2 HTP SS 32 SS 32 FP 30004174 30004187 30004172 30004185 DB 80 80 GB DB 80 80 EB DB 119 80 GB DB 119 80 EB AET AE 40 MSC 40 2 HTP SS 40 SS 40 FP 30004171 3000418...

Page 22: ...lp 585 Rev 000 Rel 001 Date 9 10 18 22 This Page Left Intentionally Blank ...

Page 23: ...lp 585 Rev 000 Rel 001 Date 9 10 18 23 ...

Page 24: ...lp 585 Rev 000 Rel 001 Date 9 10 18 24 This Page Left Intentionally Blank ...

Page 25: ... ASME installed with the drain back tank assembly in accordance with federal state and local codes 2 Maintain the drain back tank in accordance with the maintenance procedure listed in the manufacturer s provided instructions Preven tive maintenance can help avoid any unnecessary breakdown of the drain back tank and keep the system running at optimum efficiency 3 Maintain all related system compon...

Page 26: ...S Except when specifically prohibited by the applicable state law the Owner and not the Manufacturer shall be liable for and shall pay for all charges for labor or other expenses incurred in the removal repair or replacement of the drain back tank or any component part s claimed to be defective or any expense incurred to remedy any defect in the product Such charges include but are not necessarily...

Page 27: ...tive Distributor Dealer Please insert contact details Customer Installation Record Form The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim After reading the important notes at the bottom of the page please also sign this document Customer s Name Date of Installation Installation Address Product Name Serial Number s Co...

Reviews: