PVCHECK 

8

 

 

 

 

4.2. 

KEYBOARD DESCRIPTION  

The keyboard includes the following keys:  

 

 

ON/OFF

 key to switch on/off the instrument  

 

ESC/MENU

 key to exit the selected menu without confirming and to go back to 

the main menu 

 

 

 

 

 keys to move the cursor inside the various screens in order to select 

programming parameters 

ENTER

 key to confirm modifications, selected programming parameters and to 

select the function to be accessed from the menu.

 

 

GO /STOP

 key to start measurements  

 

SAVE

 key to save the measured values  

 

HELP

 key (long pressing) to access the on-line help, to view the possible 

connections between the instrument and the installation.  

key (simple pressing) to acti

vate the display’s backlighting. 

 
  

4.3. 

DISPLAY DESCRIPTION  

The display is a graphic module with a resolution of 128 x 128 dots. 

The display’s first line indicates the system’s date/time and contains 
the battery charge indicator.  

At the bottom of the display, the function of the 

ENTER

 key and the 

active mode are displayed.  

The  symbol 

 indicates  the  presence  of  an  active  radio 

connection with the remote unit SOLAR-02.  

The flashing symbol 

 indicates that the instrument is currently 

searching for a radio connection with the remote unit SOLAR-02.

 

 

  

4.4. 

INITIAL SCREEN  

When switching on the instrument, the initial screen appears for a 

few seconds. It shows: 

 

 

  The instrument model (PVCHECK) 

 

The manufacturer’s name 

  The presence of the enabled internal module for RF connection  

  The serial number (SN:) of the instrument  

  The firmware version (FW:) in the instrument's memory  

  The date of the last instrument calibration (Calibration date:)  

  

After  a  few  seconds,  the  instrument  switches  to  the  last  function 

selected

 

Summary of Contents for PVCHECK

Page 1: ...Manual PVCHECK EAN 8033772797467...

Page 2: ...PVCHECK 2 PVCHECK...

Page 3: ...te unit Pyranometer 10 5 1 5 Irradiance 11 5 1 6 DC Clamp 11 5 2 EFF EFFICIENCY TEST SETTINGS FOR PV INSTALLATIONS 12 5 2 1 Instrument settings 12 5 2 2 System parameters 13 5 2 3 Selection of the com...

Page 4: ...VING IVCK M AND LOW MEASURED RESULTS 44 7 3 OPERATIONS WITH RESULTS 45 7 3 1 Recalling on the display the PV efficiency results 45 7 3 2 Recalling on the display the results of IVCK M and LOW measurem...

Page 5: ...xists In this manual and on the instrument the following symbols are used CAUTION observe the instructions given in this manual an improper use could damage the instrument or its components High volta...

Page 6: ...easured circuits reads Circuits are divided into the following measurement categories Measurement category IV is for measurements performed at the source of the low voltage installation Examples are e...

Page 7: ...power at PV modules strings outputs Measurement of irradiation W m2 by means of a reference cell connected to the optional remote unit SOLAR 02 Measurement of module and environmental temperature by...

Page 8: ...of the internal batteries When battery charge decreases to a minimum level the symbol appears on the display In this case stop testing and replace the batteries according to the indications given in 9...

Page 9: ...of the front part of the instrument CAPTION 1 Input for irradiation measuring probe 2 Input for auxiliary temperature measuring probe DC current clamp IVCK EFF 3 P N inputs for DC voltage IVCK EFF Ins...

Page 10: ...y is a graphic module with a resolution of 128 x 128 dots The display s first line indicates the system s date time and contains the battery charge indicator At the bottom of the display the function...

Page 11: ...e different settings of the instrument Settings will be maintained also after switching off the instrument 5 1 1 General 1 Position the cursor onto General by using the arrow keys and confirm with ENT...

Page 12: ...row keys 4 Press the SAVE key to save the settings made the message Data saved will be displayed for a few seconds Press the ESC MENU key to exit without saving and go back to the previous screen 5 1...

Page 13: ...the message Data saved will be displayed for a few seconds Press the ESC MENU key to exit without saving and go back to the previous screen CAUTION The 0 W m2 setting for parameter Irr min IVCK allows...

Page 14: ...erator 2 Press the ENTER key The instrument shows the following options System parameters and Instrument settings 3 Use the arrow keys to select Instrument settings and confirm with ENTER The instrume...

Page 15: ...nstallation expressed in kW Range coefficient of power variation with temperature characteristic parameter of PV modules range 1 00 0 01 C NOCT rated operating temperature of the cell characteristic p...

Page 16: ...ended to select T Env correction Corr Type Temperature used Tcel Calculation of nDC Ref where Symbol Description Measuring unit Gp Irradiance measured on PV module surface W m2 GSTC Standard Irradianc...

Page 17: ...rrow keys to select Settings and confirm with ENTER The instrument shows the following screen 4 Using the arrow keys it is possible to set the maximum limit value of Rpe resistance which the instrumen...

Page 18: ...tings saved for test voltage also affect the settings for the insulation measurement contained in the IVCK measurement MENU IVCK 5 5 IVCK SETTINGS FOR IVCK QUICK TEST The purpose of this measurement i...

Page 19: ...nstrument Allowable values 0 25 The value between brackets 4 indicates the reading error of the instrument in Voc measurement Tol Isc percentage value of the desired limit tolerance set by the operato...

Page 20: ...5 9 99A 0 01A Isc Impp Toll Negative tolerance for Pmax provided by the module manufacturer 0 25 0 0 1 100 Tol Pnom 25 0 99W 1 Toll Positive tolerance for Pmax provided by the module manufacturer 0 25...

Page 21: ...ss the SAVE key to save the name of the new module thus defined or the ESC MENU key to exit without saving 6 Insert the value of each parameter see Table 1 according to the possible datasheet of the M...

Page 22: ...arrow keys Keep the arrow keys pressed to carry out a quick setting of the values If the value of any parameter is unknown press and hold the HELP key for a few seconds to set the default values 7 Pr...

Page 23: ...safety while making the connections disable the system being measured by means of the switches breakers upstream and downstream of the DC AC converter inverter Fig 4 Connection of instrument for effic...

Page 24: ...itive output conductor of the string respecting the direction of the arrow found on the clamp itself as indicated in 10 Fig 4 Connection of instrument for efficiency measurement on a PV installation 1...

Page 25: ...icate that the unit has detected the data with solar irradiation minimum threshold set see 5 1 5 22 With the message READY shown on the display wait for approximately 1 minute in order to take a certa...

Page 26: ...1 Select the option NO as regards the type of remote unit to be used during EFF test see 5 1 4 set the full scale of the DC clamp see 5 2 1 a possible correction factor of the DC clamp see 0 the integ...

Page 27: ...he instrument s display 9 At any time it will be possible to analyze the current recording status by pressing the MENU key The following information will be shown Starting date and time of recording T...

Page 28: ...mode is suitable to carry out a test session on a considerable number of strings as quickly as possible 0 recommended 700W m2 the instrument carries out all tests provided for I V test manages all co...

Page 29: ...n real time Tc value of module temperature see 5 5 1 Voc Isc section with display of result OK NO of Voc and Isc measurement Ri the value in brackets may be NO selected test voltage see 5 5 1 The valu...

Page 30: ...the time necessary to obtain a steady value 12 The value of insulation resistance is shown in field Ri and the message OK appears in case the result of the test is positive measured value higher than...

Page 31: ...Switch on the instrument by pressing the ON OFF key 2 Irradiance measurement is carried out in one of the following modes Measurement by reference cell directly connected to PVCHECK Measurement by ref...

Page 32: ...nclinometer M304 11 Connect the output of the cell corresponding to the type of module being tested to the IRR input of the instrument using the cable supplied with the cell or to the PYRA CELL input...

Page 33: ...tial screen of IVCK mode the following values are displayed in real time Module type of module being tested Vdc value of output voltage from module string Irr irradiance from a direct measurement or S...

Page 34: ...itive measured value higher than the minimum limit value set on the instrument 19 With continuity measurement selected the instrument goes on by opening the short circuit and carrying out the test bet...

Page 35: ...esult by comparing the values measured with the average values calculated according to the previously saved measured In this case the average values calculated by the instrument are therefore particul...

Page 36: ...s according to the prescriptions IEC EN62446 guideline In general the instrument measures insulation in the following modes FIELD mode used for measuring insulation resistance of a PV field photovolta...

Page 37: ...ative pole of the PV field and the earthing Rp final value of the measurement obtained by the parallel of Ri e Ri values which is compared with the Ri min limit by the instrument key access to the sec...

Page 38: ...screen to the side 2 Press the ENTER key activate Settings and possibly change the desired parameters see 5 4 The following parameters are shown on the display Ins Test selected test voltage 250 500...

Page 39: ...reen 6 4 4 Measuring insulation STRING mode CAUTION The maximum current which can be measured by the instrument is 10A Before carrying out the measures of Insulation in STRING mode always ensure that...

Page 40: ...rement is complete the instrument provides the Ri value i e the minimum value of insulation resistance of the PV module string or of other objects being tested continuously measured during the whole d...

Page 41: ...t the test and displays the message Low voltage 6 5 MEASUREMENT OF CONTINUITY ON PV MODULES STRINGS FIELDS LOW 6 5 1 Foreword The purpose of this measurement is to test the continuity of protective co...

Page 42: ...e value of compensated resistance carry out a new compensation procedure with a resistance higher than 5 such as for example with open leads The value in Rcal is zeroed on the display 6 5 3 Measuring...

Page 43: ...instrument displays the message Measuring as shown in the screen to the side 6 At the end of measurement the instrument provides the value of resistance of the object being tested If the result is lo...

Page 44: ...4 contact service Internal instrument error Database full The number of modules added to the internal DB is 30 Module already added The name of the module has already been added to the DB Memory full...

Page 45: ...contact service Internal instrument error FRAM error contact service Internal instrument error RTC Error contact service Internal instrument error RADIO error contact service Internal instrument error...

Page 46: ...or the system 2 For each of the 3 markers Plant String and Module it is possible to assign custom labels except if already permanently assigned to another marker the message Label already assigned is...

Page 47: ...he datum has been saved in the instrument DESCRIPTION indicates the description provided by the user when saving the datum 4 Select the type of SMP datum the item Open and confirm with ENTER The instr...

Page 48: ...Numeric display 1 Select a line corresponding to a saved result and press ENTER 2 Select Open and press ENTER to open the section where measurement results are displayed as Numeric screens of measure...

Page 49: ...voltage The Rp final value of the measurement obtained by the parallel of Ri e Ri values which is compared with the Ri min limit by the instrument 7 For LOW test there are the values of the following...

Page 50: ...SC MENU key to open the main menu 4 Use the arrow keys to select PC to access data transfer mode and confirm with ENTER 5 The instrument shows the following screen 6 The instrument shows the following...

Page 51: ...f 10 TECHNICAL SPECIFICATIONS 10 1 TECHNICAL SPECIFICATIONS FOR PV INSTALLATION EFFICIENCY Accuracy is indicated as reading no of digits resolution at 23 C 5 C 80 HR DC voltage Range V Resolution V Ac...

Page 52: ...0 1 1 0 rdg 1 C 10 3 TECHNICAL SPECIFICATIONS FOR ELECTRICAL SAFETY Continuity of protective conductors LOW Range Resolution Accuracy 0 00 1 99 0 01 2 0 rdg 2dgt 2 0 19 9 0 1 20 199 1 Test current 20...

Page 53: ...ution level 2 Measurement category CAT III 300V to earth Max 1000V between inputs P N E C 10 5 GENERAL CHARACTERISTICS Display and memory Type of display LCD custom 128x128 pxl with backlighting Saved...

Page 54: ...er see 5 2 3 Corr Tcel value Mathematical relationship for nDC calculation Standard Result Tmod Tcel Measured module temp value Italian guideline CEI 82 25 OK NO Tenv Tcel Calculated module temp value...

Page 55: ...the following cases Repair and or replacement of accessories and battery not covered by warranty Repairs that may become necessary as a consequence of an incorrect use of the instrument or due to its...