4.3.2. Leakage current measurement
CAUTION
Insert the cable(s) in the middle of the clamp jaws, in order to obtain
accurate measures. Use the marks as a reference (see § 4.1.2)
Fig. 4: Measuring leakage current with direct
method in a single phase load
Fig. 5: Measuring leakage current with
indirect method in a single phase load
Fig. 6: Measuring leakage current with direct
method in a three phase load
Fig. 7: Measuring leakage current with
indirect method in a three phase load
Leakage current measurement with Direct method on earth conductors
1. Switch on the clamp by pressing the
key
2. Select the desired capacity with the
Range
key or keep in the Autorange mode
3. Open the clamp jaw and connect the clamp as shown in Fig. 4 or Fig. 6. The leakage
current value will be shown on the display
4. For Hold, Data Hold, Auto Hold and Peak Hold feature refer to § 4.2
Leakage current measurement with Indirect method
1. Switch on the clamp by pressing the
key
2. Select the desired capacity with the
Range
key or keep in the Autorange mode
3. Open the clamp jaw and connect the clamp as shown in Fig. 5 or Fig. 7. The leakage
current value will be shown on the display
4. For Hold, Data Hold, Auto Hold and Peak Hold feature refer to § 4.2
Summary of Contents for HT77N
Page 1: ...Copyright HT ITALIA 2012 Release 1 02 11 12 2012 ...
Page 3: ...Copyright HT ITALIA 2012 Versione IT 1 02 11 12 2012 ITALIANO Manuale d uso ...
Page 17: ...Copyright HT ITALIA 2012 Release EN 1 02 11 12 2012 ENGLISH User manual ...
Page 31: ...Copyright HT ITALIA 2012 Versión ES 1 02 11 12 2012 ESPAÑOL Manual de instrucciones ...
Page 45: ...Copyright HT ITALIA 2012 Ausführung DE 1 02 11 12 2012 DEUTSCH Bedienungsanleitung ...
Page 59: ......