IMP57
EN - 22
6.3.
OPERATING INSTRUMENT FOR “TYPE 3” INSTRUMENT
Operating Instruction are given according to
Table 1 - Instrument Type
definition.
6.3.1. Instrument Settings
Press
MENU
button, select
LOOP
by means
,
buttons and press
ENTER
button.
Mod.
Select by means
,
buttons the virtual button
Mod.
and by means
,
buttons the
Z2
function. The instrument shows:
L O O P
Z = - - - - -
Ω
R = - - - - -
Ω
X = - - - - -
Ω
I k S T D = - - - - A
V1-2=230V FRQ=50H
z
P-N Z2
Ω
Funz
Mod. ICAL RMT
Funz
Select by means
,
buttons the virtual button
Funz
and by means
,
buttons the function:
“
P-N
": the instrument execute the High Resolution Phase-Neutral
impedance measurement and calculate the Prospective Short circuit
Current Calculation selected.
“
P-P
": the instrument execute the High Resolution Phase-Phase
impedance measurement and calculate the Prospective Short circuit
Current Calculation selected.
“
P-PE
": the instrument execute the High Resolution Phase-ground
impedance measurement and calculate the Prospective Short circuit
Current.
ICAL
Select by means
,
buttons the virtual button
ICAL
which allows the
selection of Prospective Short Circuit current calculation according to
paragraph 6.3.2 by means
,
buttons.
RMT
:
Select by means
,
buttons the virtual button
RMT
. The instrument will
show:
IMP57 Serial Number.
Firmware
release.
calibration
date.