Chapter 8 Parameter
HD09 Series User Manual V1.1
-
35
-
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
stop
F19.13
Instant stop function
deceleration time
0.01 - 600.00s
5.00s
0.01s
○
F19.14
Voltage rerise judgement
time for Instantaneous loss
of power and no
downtime
0.00 - 10.00s
0.10s
0.01s
○
F19.15
Voltage judgement for
Instantaneous loss of
power and no downtime
0 - 999V
220V
inverter:
248V
380V
inverter:
430V
1V
×
F19.18
Protection of stall
overvoltage
0: Disabled (with braking resistance)
1: Enabled
1 1
×
F19.19
Stall overvoltage point
0 - 999V
Depende
nt on
HD09
1V
×
F19.20
Auto current limiting
selection
0: Disabled
1: Enabled in Acc / Dec running
process, but disabled in constant
speed runnng process
2: Enabled both in Acc / Dec and in
constant speed running proces
1 1
×
F19.21
Auto current limiting
threshold
20.0 - 200.0%
150.0%
0.1%
×
F19.22
Deceleration time at auto
current limiting
0.00 - 600.00s
0.00s
0.01s
×
F19.23
Enabled mode of terminal
run command
0: Rise edge enabled mode
1: Level enabled mode
0 1
○
F19.24
Action voltage of braking
unit
630 - 750V
Depende
nt on
HD09
1V
×
F19.37
Frequency adjust range
selection
Unit: Main frequency range
0: 0 - max. frequency
1: Negative maximum frequency to
maximum frequency
100 1
○