Chapter 8 Parameter
Shenzhen Hpmont Technology Co., Ltd.
-
36
-
HD09 Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
Ten: Unused
Hundreds: The range of synthetic
frequencies
0: 0 - up limitation frequency
1: Negative upper limit frequency to
upper limit frequency
F19.39
Input voltage selection
Unit : 380V input voltage
0: 380 - 460V
1: 260 - 460V
2: 200 - 460V
Ten: 220V input voltage selection
0: 200 - 240V
1: 140 - 240V
00 1
×
F19.44
LCD Backlight display time
0.0 - 999.9min
5.0min
0.1min
○
F20: Protection of Fault Parameters
F20.00
Selection for overload
prediction police check
out
00000: Enbale overload protection
10000: Disbale overload protection
00000 1
○
F20.10
Output phase loss
detection reference
0 - 50%
20%
1%
×
F20.11
Output phase loss
detection time
0.00 - 20.00s
3.00s
0.01s
×
F20.18
Auto reset times
0 - 100
0
1
×
F20.19
Auto reset interval
2.0 - 20.0s/times
5.0
s/times
0.1
s/times
×
F20.21
Type of third latest (the
last) fault
-Lu-: DC bus undervoltage
E0001: Acc overcurrent
E0002: Dec overcurrent
E0003: Costant overcurrent
E0004: Acc overvoltage
E0005: Dec overvoltage
E0006: Constant overvoltage
E0007: Stall overvoltage
E0008: Fault of power module
E0009: Heatsink overheat
E0011: CPUfault
E0012: Parameters auto-tuning fault
E0013: Contactor is not actuated
0 1
*