HP StorageWorks XP12000 Disk Array Site Preparation Guide
AC line voltage requirements
50-amp, single-phase DKC
30-amp, single-phase DKC
Table 23. 50-amp, 50 or 60 Hz, single-phase DKC operation
Nominal rated voltage (Vac)
Parameter
200
208
1
1 60 Hz only.
220
230
240
Minimum operating voltage (Vac)
184
191
202
212
221
Maximum operating voltage (Vac)
212
220
233
244
254
Rated line current per power cord (Arms)
22.6
21.7
20.5
19.6
18.8
Number of power cords
2
2
2
2
2
Recommended circuit breakers
50A
50A
50A
50A
50A
Number of circuit breakers
2
2
2
2
2
Dropout carry-through time at minimum line voltage (ms)
60
60
60
60
60
Table 24. 30-amp, 50 or 60 Hz, single-phase DKC operation
Nominal rated voltage (Vac)
Parameter
200
208
1
1 60 Hz only.
220
230
240
Minimum operating voltage (Vac)
184
191
202
212
221
Maximum operating voltage (Vac)
212
220
233
244
254
Rated line current per power cord (Arms)
11.3
10.9
10.3
9.8
9.4
Number of power cords
2
2 Units with only two power cords require only two circuit breakers.
4
4
4
4
4
Recommended circuit breakers
30A
30A
30A
30A
30A
Number of circuit breakers
4
4
4
4
4
Dropout carry-through time at minimum line voltage (ms)
60
60
60
60
60