Site Requirements
49
Shock
Heat dissipation and power consumption
Table 17
describes the heat dissipation and power consumption of the
XP12000 when fully loaded with the maximum number of disk drives.
Table 16. Shock specifications
Condition
Specification
Operating
None
Nonoperating
8 G, 15 ms
Shipping and storage (product packed in
factory packing)
Horizontal:
1
Incline impact: 1.22 m/s
Vertical:
2
Rotational edge: 0.1 m
1 See ASTM D5277-92 Standard Test Methods for Performing Programmed Horizontal
Impacts Using an Inclined Impact Tester.
2 See ASTM D1083-91 Standard Test Methods for Mechanical Handling of Unitized Loads
and Large Shipping Cases and Crates.
Table 17. Heat dissipation and power consumption specifications
Parameter
DKC Each DKU
Full array
(1 DKC and 4 DKUs)
Power consumption (kVA)
8.45
7.50
38.45
Heat dissipation (kW)
8.02
6.75
35.02
BTUs per hour
27370
23036
119514
kcal per hour
6897
5805
30117