Power requirements may require modi
fi
cation of the facility’s existing power capabilities
by a quali
fi
ed electrician. The required wall outlet for the United States and Canada is
rated at 250VAC 16 amps (see
).
Y
X
G
1
2
3
1
Line x
2
Line y
3
Ground
Figure 3 Wall outlet (NEMA L6-20R rated 250VAC 20 amps)
Two dedicated wall outlets and a 20-amp circuit breaker are required to provide power
to the library. Outside of North America, replace the supplied power cord(s) with
harmonized 3 x 1.5 mm
2
power cord(s) that meet local requirements, and install the
appropriate wall outlet.
WARNING!
This product can only be used with an HP approved power cord for your speci
fi
c
geographic region. Use of a non-HP approved power cord may result in: 1) not
meeting individual country speci
fi
c safety requirements; 2) insuf
fi
cient conductor
ampacity that could result in overheating with potential personal injury and/or property
damage; and 3) an unapproved power cord could fracture resulting in the internal
contacts being exposed, which potentially could subject the user to a shock hazard. HP
disclaims all liability in the event a non-HP approved power cord is used.
NOTE:
More information on the electrical requirements is provided in the
HP StorageWorks
ESL E-Series Pre-Installation Site Survey
.
WARNING!
To avoid damage to the library and risk to personal safety, the library must be
connected to a grounded electrical outlet.
16
Unpacking the library
Summary of Contents for StorageWorks ESL E Series
Page 8: ...8 ...