Chapter 5
Removing and Installing HP Rack Storage/12 Components
39
3. Loosen the two thumbscrews securing the RS/12 SCSI card to the chassis.
4. Pull the RS/12 SCSI card out of the chassis and place it in an anti-static
container.
Removing the Connector Filler Panel
Remove the connector filler panel if you are installing a second RS/12 SCSI card.
1. Loosen the two thumbscrews securing the adapter filler panel to the
chassis.
2. Pull the filler panel out of the chassis.
Installing the RS/12 SCSI Card
1. Insert the RS/12 SCSI card until it is fully seated in the chassis.
2. Secure the RS/12 SCSI card to the chassis with two thumbscrews.
3. Connect the SCSI cable from the host system to the RS/12 SCSI card.
NOTE
The current SCSI channel configuration is restored from
memory. The configuration can be changed by recycling AC
power.
Replacing the Hot-Swap Power Supply
The power supply and fan module are removed as a unit from the chassis (see
Figure 5-6).
NOTE
The remaining power supply supplies power to the HP Rack
Storage/12 while the power supply is replaced.
Replacing the hot-swap power supply requires completing the following tasks:
•
Remove the power supply
•
Separate the fan module from the power supply
•
Attach an operating fan module to an operating power supply
•
Install the power supply