Removing and replacing a heatsink
Removing and replacing a heatsink
This procedure shows a standard heatsink as an example. The replacement process is the same for both the standard and high-
performance heatsinks.
Prerequisites
Prerequisites
Before you perform this procedure, make sure that you have the following items available:
T-20 screwdriver
Alcohol wipe
Procedure
Procedure
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Remove the server from the rack .
6. Allow the existing heatsink to cool.
7. Remove the heatsink:
CAUTION:
CAUTION:
To prevent mechanical damage or depositing oil on your hands or other contaminants to the heatsink contact
surface, hold the heatsink only by the edge of its baseplate. Do not touch the heatsink fins.
CAUTION:
CAUTION:
Heatsink screws must be tightened and loosened in alternating sequence as shown on the heatsink label.
a. Use a T-20 screwdriver to loosen the captive screws in the sequence specified on the heatsink label.
b. Lift the heatsink away from the system board.
Removing and replacing a heatsink
102
Summary of Contents for ProLiant DL345 Gen10 Plus
Page 47: ...Customer self repair 47 ...
Page 48: ...Customer self repair 48 ...
Page 49: ...Customer self repair 49 ...
Page 50: ...Customer self repair 50 ...
Page 68: ...Removing a riser cage 68 ...
Page 76: ...Removing and replacing the cable management arm 76 ...
Page 77: ...Removing and replacing a power supply Removing and replacing a power supply 77 ...
Page 135: ...System battery replacement System battery replacement 135 ...
Page 139: ...Removing and replacing the system board Removing and replacing the system board 139 ...
Page 149: ...Troubleshooting NMI functionality Troubleshooting resources Troubleshooting 149 ...
Page 152: ...Diagnostic tools Diagnostic tools 152 ...
Page 188: ...HPE Basic Drive LED definitions 188 ...
Page 193: ...Fan bay numbering The arrow points to the front of the server Fan bay numbering 193 ...
Page 197: ...Storage cabling Storage cabling 197 ...
Page 198: ...Drive power cabling Drive power cabling 198 ...
Page 201: ...2 SFF drive power cabling 2 SFF drive power cabling 201 ...
Page 202: ...Storage controller cabling Storage controller cabling 202 ...
Page 232: ...Energy pack cabling Energy pack cabling 232 ...
Page 234: ...Storage controller backup power cabling 234 ...
Page 235: ...M 2 SATA SSD cabling M 2 SATA SSD cabling 235 ...
Page 237: ...Fan cabling Fan cabling 237 ...
Page 238: ...OCP bandwidth upgrade cabling OCP bandwidth upgrade cabling 238 ...
Page 239: ...Serial port cabling Serial port cabling 239 ...
Page 240: ...Chassis intrusion detection switch cabling Chassis intrusion detection switch cabling 240 ...