Removing a riser cage
Removing a riser cage
Procedure
Procedure
2. If installed, release the cable management arm .
3. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4. Do one of the following:
Extend the server from the rack .
Remove the server from the rack .
6. Do one of the following:
If an expansion card with internal cables is installed on the riser, disconnect the cables from the card.
If cables are connected to the riser SlimSAS ports, disconnect the cables.
7. When the rear 2 SFF drive option is mounted on the secondary riser cage, disconnect the 2 SFF drive backplane cables.
8. Remove the riser cage:
Primary riser cage
Secondary riser cage
Removing a riser cage
67
Summary of Contents for ProLiant DL345 Gen10 Plus
Page 47: ...Customer self repair 47 ...
Page 48: ...Customer self repair 48 ...
Page 49: ...Customer self repair 49 ...
Page 50: ...Customer self repair 50 ...
Page 68: ...Removing a riser cage 68 ...
Page 76: ...Removing and replacing the cable management arm 76 ...
Page 77: ...Removing and replacing a power supply Removing and replacing a power supply 77 ...
Page 135: ...System battery replacement System battery replacement 135 ...
Page 139: ...Removing and replacing the system board Removing and replacing the system board 139 ...
Page 149: ...Troubleshooting NMI functionality Troubleshooting resources Troubleshooting 149 ...
Page 152: ...Diagnostic tools Diagnostic tools 152 ...
Page 188: ...HPE Basic Drive LED definitions 188 ...
Page 193: ...Fan bay numbering The arrow points to the front of the server Fan bay numbering 193 ...
Page 197: ...Storage cabling Storage cabling 197 ...
Page 198: ...Drive power cabling Drive power cabling 198 ...
Page 201: ...2 SFF drive power cabling 2 SFF drive power cabling 201 ...
Page 202: ...Storage controller cabling Storage controller cabling 202 ...
Page 232: ...Energy pack cabling Energy pack cabling 232 ...
Page 234: ...Storage controller backup power cabling 234 ...
Page 235: ...M 2 SATA SSD cabling M 2 SATA SSD cabling 235 ...
Page 237: ...Fan cabling Fan cabling 237 ...
Page 238: ...OCP bandwidth upgrade cabling OCP bandwidth upgrade cabling 238 ...
Page 239: ...Serial port cabling Serial port cabling 239 ...
Page 240: ...Chassis intrusion detection switch cabling Chassis intrusion detection switch cabling 240 ...