Figure 16 Routing of the Main Power Cords
Electrical Requirements and Limitations
Before physically installing a storage system, verify that the operating site has the necessary electrical
circuitry. Each storage system requires 4 (200 - 240) Volt, 30 Amp outlets or 2 outlets if only the
bottom half of the cabinet is occupied. For proper redundant power protection, power should be
supplied from two or more power sources.
Use the approximate current requirements for storage server components listed in
Table 15 (page 34)
to estimate the current requirements for a specific system configuration.
Power and Heat Specifications
The following table lists the electrical power requirements for the HP P10000 3PAR Storage Systems.
Table 15 HP P10000 3PAR Storage System Power Requirements
2 Meter Cabinet
9,984
Max. Watts per Cabinet (fully
populated)
34,075
Max. BTUs/hour per cabinet
(fully populated)
200 - 240
Input Voltage (VAC)
50 - 60
Frequency (Hz)
30A per PDU (de-rated to 24A)
Circuit Breaker Max
200
Drive Chassis (no magazines)
(4) L6-30P Plug (North America
and Japan) (4) IEC-60309 Plug
(EU and Korea)
Power Connectors
Idle
Transactional
Node Pair (fully populated)
34
Power Requirements