Table 4 V400/V800 Storage System Capacity Specifications
(continued)
V800
V400
Feature
0-8 with 2 nodes 0-16 with 4 nodes
0-32 with 8 nodes
0-8 with 2 nodes 0-16 with 4 nodes
10 GB /s iSCSI Host Ports
0-48 (2 node) 0-96 (4 node) 0-144 (6
node) 0-192 (8 node)
0-48 (2 node) 0-96 (4 node)
Fibre Channel host ports (four-port
adapters)
1
0-32 10 Gb/s
0-16 10 Gb/s
iSCSI host ports
16-1,920
16-960
Number of drives
1
2.3-1600 TB
2.3-800 TB
Raw capacity (approx.)
1
6,400
3,200
Architectural maximum number of
drives
RAID 0, 1, 5, 6, 10, 50
RAID 0, 1, 5, 6, 10, 50
RAID levels
2:1 - 8:1
2:1 - 8:1
RAID 5 data to parity ratios
300 GB 15K FC, 600 GB 15K FC, 2
TB NL, 100 GB SSD, 200 GB SSD
300 GB 15K FC, 600 GB 15K FC, 2
TB NL, 100 GB SSD, 200 GB SSD
Drive capacities (GB’s approx.)
1
Number of drive chassis
2
2–48
2–24
DC4
0.053
0.053
Energy consumption efficiency
3
1
Levels, ratios, and capacities all mixable within the same storage server. 1 GB=1,000,000,000 bytes.
2
A single drive chassis holds up to 40 drives in 4U of space within an EIA-standard rack.
3
Japan Green Law statement of compliance: The energy consumption efficiency value has been calculated per requirements
for Category-G Magnetic Disk Drive Units by dividing the power consumption, measured according to the definition
in the Law Concerning the Rational Use of Energy, by the storage capacity defined in the Energy Conservation Law.
The efficiency value is based on a host-maximized V800 configuration using 600GB drives.
Power and Heat Specifications
The following table lists the electrical power requirements for the HP P10000 3PAR Storage Systems.
Table 5 HP P10000 3PAR Storage System Power Requirements per Cabinet
2 Meter Cabinet
9,984
1
Max. Watts per Cabinet (fully
populated)
34,075
Max. BTUs/hour per cabinet (fully
populated)
200 - 240
Input Voltage (VAC)
50 - 60
Frequency (Hz)
30A per PDU (de-rated to 24A)
Circuit Breaker Max
200
Drive Chassis (no magazines)
(4) L6-30P Plug (North America
and Japan) (4) IEC-60309 Plug
(EU and Korea)
Power Connectors
Idle
Transactional
2
Node Pair (fully populated)
630
705
Watts
2,150
2,406
BTUs/hour (fully populated)
Power and Heat Specifications
11
Summary of Contents for P10000
Page 30: ...Figure 12 Power Supplies Within the Power Domains 30 Power Requirements ...