HP Intelligent PDU web interface 55
SNMP Managers tab
This screen contains controls that enable administrators to enter information for SNMP managers. SNMP
managers are computers that use the HP Power MIB to request information from the iPDU.
To configure SNMP managers:
1.
Enable the SNMP manager configuration for up to five servers.
2.
Enter the IP address for each SNMP manager in the IP Address field.
IMPORTANT:
SNMP managers cannot communicate with the iPDU until the IP address is
entered on the SNMP Managers tab. Entering the IP address 0.0.0.0 allows SNMP access
from any computer. Use a specific IP address for each SNMP manager to avoid
compromising the iPDU security.
3.
Enter the Read community string for each SNMP manager.
4.
Enter the Write community string for each SNMP manager.
5.
Configure the access type for each SNMP manager.
o
RO—Read Only
o
RW—Read/Write
6.
Do one of the following:
o
Click
Save Settings
to save the information.
o
Click
Undo Changes
to undo the changes.
o
Click
Help
to view online help.