Technical Specifications
175
Core Switch 2/64 V4.1 Installation Guide
Facility Requirements
The facility where the Core Switch 2/64 is in use must meet the following
requirements to provide for correct operation:
■
Power requirements for a physical inlet:
— Input Power Requirements: 200-240 VAC, 12A, 50-60 Hz
— Recommended Power Connector: IEC 320, EN60320 C19-Angled,
16A/250VAC
■
Adequate supply circuit, line fusing, and wire size, as specified by the
electrical rating on the chassis nameplate.
■
An air flow of at least 350 cubic feet per minute, available in the immediate
vicinity of the Core Switch 2/64.
■
The power specifications listed in
■
The environmental specifications listed in
■
The electrical interference must be less than the levels stated in the standards
listed in the Immunity row in
■
If the Core Switch 2/64 will be installed in an EIA rack:
— Ensure that all equipment installed in the rack has a reliable branch circuit
ground connection, and does not rely on a connection to a branch circuit,
such as a power strip.
— Ensure that the rack is balanced and mechanically secured to ensure
stability in the event of an earthquake.
— Verify that the additional equipment does not exceed the rack’s weight
limits.
Summary of Contents for AA-RS2WC-TE
Page 12: ...Contents 12 Core Switch 2 64 V4 1 Installation Guide ...
Page 34: ...Overview 34 Core Switch 2 64 V4 1 Installation Guide ...
Page 88: ...Installing and Configuring the Core Switch 2 64 88 Core Switch 2 64 V4 1 Installation Guide ...
Page 168: ...Running Routine Operations 168 Core Switch 2 64 V4 1 Installation Guide ...
Page 198: ...Technical Specifications 198 Core Switch 2 64 V4 1 Installation Guide ...
Page 224: ...Setting Up and Configuring Modems 224 Core Switch 2 64 V4 1 Installation Guide ...